6
EDS 4000 programmable
Status: 16.06.2015
HYDAC
ELECTRONIC
GMBH
Part No.: 669737
E
7 Settings
By using the programming unit HPG 3000, it is possible to make the following settings in the
EDS 4000:
7.1 Switch point settings
This sets the switch value at which the switching output will switch when the
value is exceeded (above or below) according to its pre-set switching
direction (see 7.3).
Abbreviations: “
SP.1
“
= Switching point 1
“
SP.2
“ = Switching point 2
(only on units with two switching points)
7.2 Hysteresis
settings
(Switch-back point)
This sets a hysteresis to the switching point. The switching output switches
back if the value falls below the switch-back point. The switch-back point is
determined by the pre-set hysteresis (switch-back point = switching point
minus hysteresis).
Abbreviations: "
HYS.1
“
= Hysteresis SP1
"
HYS.2
”
= Hysteresis SP2
(only on units with two switching points))
7.3 Switching direction (N/O or N/C-function)
The switching direction determines if the switching function is to be normally
open or normally closed. (on = N/O-function / oFF = N/C-function)
Abbreviations: "
S.d.1
"
= Switching direction SP1
"
S.d.2
“
= Switching direction SP2
(only on units with two switching points)
7.4 Switch on delay
Time in milliseconds [ms] which must elapse, once the switching point has
been reached or exceeded, before switching will occur.
Abbreviations: "
T.on1
"
= Switch on delay [ms] SP1
"
T.on2
"
= Switch on delay [ms] SP2
(only on units with two switching points))
7.5 Switch off delay
Time in milliseconds [ms] which must elapse, once the pressure has fallen
below the particular switch-back point, before switching will occur.
Abbreviations: "
T.oF1
"
= Switch off delay
[ms] SP1
"
T.oF2
"
= Switch off delay
[ms] SP2
(only on units with two switching points)
Summary of Contents for EDS 4000
Page 14: ...14 EDS 4000 programmierbar Stand 16 06 2015 HYDAC ELECTRONIC GMBH Mat Nr 669737 D ...
Page 28: ...14 EDS 4000 programmable Status 16 06 2015 HYDAC ELECTRONIC GMBH Part No 669737 E ...
Page 42: ...14 EDS 4000 programmable Edition 16 06 2015 HYDAC ELECTRONIC GMBH Code article 669737 F ...
Page 43: ...Notizen Notes Notes ...