34 / 51
Data transfer in progress.
Strapping table values have been successfully sent to the instrument indicated by the Ok status after each value. If only part of the table is successfully sent ensure
that the values in your table do not exceed the maximum values defined in your measurement configuration.
Supplementary procedure for setting the 4 … 20 mA current to output volume readings (using HyView)
Step
Action
Data entered/value selected
1
Click on Outputs menu.
n/a
2
Go to user function 1.3.1 ”Current 1 item” to select measurement function.
Volume
3
Go to user function 1.3.2 ”Current 1 range” to set fault status
4 … 20 mA
4
Go to user function 1.3.3 “Scale I1 min” to enter volume value for the minimum output (4 mA)
0.50 m³
5
Go to user function 1.3.3 “Scale I1 max” to enter volume value for the maximum output (20 mA)
16.80 m³
6
Save the new configuration to disk by clicking on ‘Save to disk’ and download it onto the VF04 2-wire using the
‘Send to’ button.
n/a
7
Press close to exit the configuration menu.
n/a