COMMISSIONING
After all installation procedures are finished, the luminaire operation needs to be verified. Follow the instructions below and
pay attention to the state of the led indicators:
1. Switch on the luminaire power supply. The luminaire should signal battery charging or its charged status.
2. After 36 hours turn off luminaire power supply or run B TEST. The luminaire will go automatically into emergency operation
and will operate for up to few hours over the rated emergency operation time.
3. Switch the power supply back on after the light source turns off.
4. After 24 hours the battery is again fully charged and the luminaire is ready for operation.
MAINTENANCE
Luminaire should be cleaned with a damp cloth according to building maintenance plan.
Do not use abrasive cleaners, solvents, substances and cleaning agents containing alcohol to clean the lampshade.
The light source used in this luminaire may only be replaced by the manufacturer, his service agent or a similar qualified person.
Battery replacement procedure
if nominal emergency operating time isn’t met (follow the drawings in installation procedure):
1. Turn off luminaire power supply and remove the lampshade. Disconnect battery from emergency module. In case
a thermostat and heater are used on the battery pack (luminaire with extended temperature range), disconnect the blue
and brown wires from power supply connectors.
2. Replace battery according to the type specified on battery label.
3. Connect and mount the replaced battery (reverse of step 1).
4. Mount the lamp shade.
5. Perform the commissioning procedure.
STORAGE
The luminaire should be stored no longer than 6 months from the date of purchase, in a dry place with an ambient temperature
range of -10 – +30˚C.
WARRANTY
Warranty is valid and enforceable only when manufacturer’s recommendations are preserved, and the installation and usage
are proper. Warranty is granted for a period of 12 months from the date of sale, unless the luminaire has been sold under
different contract conditions. The warranty is excluded in case of misuse, unsuitable use, wrong connection or mechanical
defects of the luminaire caused by the client.