Autonomous emergency lighting luminaire
5/8
IMM - PRIMOS SGN LED - ST_AT_CT - PL_EN V02
IP65
PRIMOS SGN LED
INSTALLATION AND MAINTENANCE MANUAL
MOUNTING TYPE
Directly to the wall or ceiling.
For other mounting types see: „Mounting accessory for PRIMOS
family of luminaires” in product data sheet
OPERATING MODE
NM
–
NON-MAINTAINED – luminaire operates in emergency
mode after power supply failure
M
–
MAINTAINED – lighting provided all the time, in case
of power supply failure switches automatically into
emergency mode
N
–
NIGHT – luminaire operates in emergency mode after
power supply failure, mains operation controlled from
the main unit of central management system (CT only)
SYSTEM VARIANT
ST
–
STANDARD – tests commissioned manually
AT
–
AUTOTEST – internal components, battery and light
source tests being performed automatically
CT
–
CENTRALTEST – internal components, battery and light
source tests being performed on command from the
main unit of central management system
TESTS
The microcontroller-based control and test unit performs automatically (AT) or on order from the central management system (CT) or by
manual execution (ST) two types of tests:
TEST A
–
internal components and light source test lasting 60 seconds – performed every 30 days for the AT system variant
TEST B
–
internal components, light source and operation duration test (till the battery is fully discharged) – performed every 360 days for the AT system
variant
TECHNICAL DATA
Supply voltage
230V AC 50/60Hz
Power consumption
< 4VA
Power factor
0,4
Protection class
II
Ingress protection
IP65
Light source type
LED strips
1)
Light colour temperature
5000K
Colour rendering index
70
Light source power
1W
Light source lifespan
> 50 000h
Battery type
Ni-Cd, Ni-MH
Battery voltage
4,8V
Battery capacity
1,0Ah; 1,6Ah
Battery recharging time
< 24h
Emergency operation time
1h; 3h
Ambient temperature range
TS: +5 – +45˚C;
TE:
2)
-20 – +45˚C
Supply cable cross-section area
0,5 – 2,5mm
2
Supply cable diameter
≤ 13mm
Communication cable diameter
≤ 7mm
Suitable for through wiring
YES
Suitable for surface wiring
YES
1)
Non-exchangeable, but serviceable light source;
2)
Extended temperature range version
SAFETY
•
During the installation and usage of emergency luminaires, follow the national safety rules as well as generally accepted technical rules
•
Supply voltage should never be removed from the permanent phase by any external switches, relays or contactors (BMS, wall switch, etc.)
•
During usage of emergency luminaires keep a register of inspection reports
•
Luminaire installation or maintenance has to be preceded by turning off the power supply and battery
•
Ensure that all foreign bodies are removed before the luminaire power is switched on
•
The luminaire is to be used undamaged and in accordance with specifications
The above-mentioned luminaire is a fire protection equipment and therefore falls within relevant standards and regulations.
NOT OBEYING THE SAFETY INSTRUCTIONS AND RECOMMENDATIONS CAN CAUSE LIFE THREAT OR EVEN DEATH
Not obeying this instruction manual can result in luminaire damage and loss of warranty
EN