AC Output Wiring Instructions:
Step 1: Disconnect the unit from the battery by removing the battery cables. Turn the Power Tower
OFF before disconnecting the batteries. Disconnect any inputs if present. Turn off main
output breaker on the inside of the cabinet.
Step 2 (120V Version): Connect the GND (green/yellow), Line (black), and neutral (white) wires from
the AC output to the proper circuit breaker panel with the panel OFF.
Step 2 (120V/240V Version): Connect the GND (green/yellow), Line 1 (black), Line 2 (typically red)
and neutral (white) wires from the AC output to the proper circuit breaker panel with the
panel OFF.
Maximum Power When using split phase configuration:
• L1 to N = Max 3000W (120V)
• L2 to N = Max 3000W (120V)
or
• L1 to L2 to N = Max 6000W (240V)
or
• L1 To L2 = Max 3000W (240V)
• L1 to N = Max 1500W (120V)
AC Generator/Grid Input Wiring Instructions:
For easy installation and compatibility, the Power Tower has been outfitted with two (2) L14-30
receptacles. These receptacles match the most common generator plug type (120/240V) plugs. A
simple extension cord between both will enable quick installation. Ensure all local electrical codes
are met when wiring the input.
ALWAYS ENSURE THAT BOTH INPUT PLUGS ARE FED BY THE SAME
SOURCE. The inputs must use the same wave form and sinusoidal timing, therefore a single source
must be used. For example, a single generator must be used
NEVER two (2) different generators
unless they have synchronization capability. When powering from the grid, two separate circuits
can be used as both wave forms should be identical but both inputs should use the same L-N. Do
not split a 240V output into two (2) 120V lines and input into two (2) separate plugs.
A 120V Power Tower will not accept an incoming 240V input as it draws from a single hot lead of
the L14-30 receptacle. The 120V/240V version will accept only 240V input as it will pull power
from both hot leads.
AC Input Wiring Instructions:
Step 1: Ensure generator or input grid power is off.
Step 2: Connect input source to Power Tower using one (1) or both input plugs. A L14-30P can be
purchased from a local electrical supplier or a complete compatible extension cord
can be used.
Summary of Contents for POWER TOWER 120V
Page 2: ...2 Batt Pack Energy User manual English...
Page 4: ...4 Power Tower User manual English MANUAL INDEX...
Page 6: ...6 Power Tower User manual English OVERVIEW SECTION 1...
Page 8: ...SAFETY INFORMATION SECTION 2...
Page 11: ...INSTALLATION SECTION 3...
Page 16: ...GROUNDING SOLAR WIRING SECTION 4...
Page 19: ...SYSTEM CONFIGURATION SECTION 5...
Page 28: ...SPECIFICATIONS SECTION 6...
Page 33: ...WARRANTY SECTION 7...
Page 36: ...DISPOSAL SECTION 8...
Page 38: ...APPENDIX SECTION 9...
Page 41: ...41 Power Tower User manual English INVERTER Figure 8...
Page 42: ...POWER TOWER...
Page 43: ......
Page 44: ...POWER TOWER...