3) Configuring the Poseidon with a web browser 

 

Enter the IP address of the device to the address field in your web browser, or run UDP Config and 
click the IP address in the list of devices.  
 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Current  Value  –  current  reading  of  the  corresponding  connected  sensor.  “–999.9”  means  that 
the sensor is not available or was initialized only after the device was powered up. 

 

Safe Range – range of readings considered OK (no alarm).  

 

Alarm Alert – defines, for each sensor, whether alarm alerts are enabled and their destination. 

 

“For more information” – info about the servicing organization, configurable in “Telnet setup”. 

 
Retrieving current readings 

 

 

XML – /values.xml file, format described using XSD – for download on the main page, detailed 
comments on XML structure are available in the manual. 

 

SNMP – the poseidon.mib description file can be downloaded from the main page. The SNMP 
ports (defaults are 161 and 162) can be changed in Flash setup.

 

 

Modbus/TCP  –  structure  description  is  available  in  the  manual,  or  in  application  examples. 
Standard port 502 is open for reading. 

 

Device name

 

 

This text can be changed, see 

the manual for details

 

Description of SNMP 

MIB and values.XML

 

Unique sensor ID 

(serial number)

 

Alert to a reading out 

of the safe range

 

 

 

Device IP address

 

 

IP adresa za

ř

ízení

 

 

Sensor input No.

 

Reading at the last 

page update

 

Alarm definition for 

each input

 

Detailed configuration 

Flash setup

 

Summary of Contents for Poseidon 3268

Page 1: ...r Dry Contact output 600 005 Temp 1Wire 3m Temperature sensor 3m cable 1m 600 242 10m 600 056 Poseidon 3268 1 5 Temperature or humidity sensors IT bus interface Temp 1Wire or Humid 1Wire RJ12 jack must click in 1 3 Connect the power adapter to an outlet 230 110V and to the Poseidon 12V power supply connector 1 6 Connect Poseidon to the Ethernet patch cable to switch or cross over cable to PC 1 2 O...

Page 2: ... Temp humidity sensor installs into a RACK as a 1U device Humidity sensor 3m cable 1m 600 278 Hub to connect up to 5 sensors 10cm cable Hub to connect 2 sensors 3m cable Power detector control 110 230V mains voltage detector I1 I4 of a Poseidon and switch connect to O1 O2 address UDP Config is located in the root of the Windows and Linux version or it can be group com Software UDP UDP Config The p...

Page 3: ...eir destination For more information info about the servicing organization configurable in Telnet setup Retrieving current readings XML values xml file format described using XSD for download on the main page detailed comments on XML structure are available in the manual SNMP the poseidon mib description file can be downloaded from the main page The SNMP ports defaults are 161 and 162 can be chang...

Page 4: ... tab click Autodetect Sensors in the lower right hand corner Controlling the outputs In the General Setup tab in the Output Settings section in the upper left hand corner set an output value and click Apply Changes Flash Setup allows you to Set up sensor names safe ranges for alarms and alarm alert destinations Monitor current sensor readings set a refresh interval Select temperature units C F K S...

Reviews: