Port 4 – Dry contact inputs
Three volt-free contacts can be connected to the
terminal block against a single common pin.
The inputs are electrically connected to the power
supply.
Unconnected inputs read as “
0 (Off)
”.
Activated inputs (closed contacts) read as
“
1 (On)
”, resistance against the Common pin
must not exceed 500Ω.
Specifications:
Maximum wiring length:
50m
Supported sensors:
Any contact without external voltage
Per-input alarm settings:
Alarm activation and state (0/1), configured over WWW - Poseidon
Flash setup.
o
Alarm inactive
o
Alarm when the contact is opened or closed
o
Alarm whenever the contact is open
Possible alarm responses:
Common setting for all inputs
o
No response
o
Alarm alert sent as a SNMP trap
o
Alarm alert sent by e-mail or text message (SMS)
o
Alarm alert sent as a SNMP trap as well as by e-mail or SMS
Polling period:
800ms
Range of sensor IDs:
Inputs use IDs from 1 to 9.
Sensor names:
Sensors can be named using up to 12 characters
Disconnected sensor detection:
None, disconnected sensor reads as “
O (Off)
”.