I. Overview

This product is DC ground fault tester of new generation. It applies to all

DC system in any voltage class, equipped with high-precision measured clamp
meter, expanded the measured range and strengthened the anti-interference
ability by processing many kinds of signal. Adopted excellent method of
calculation and advanced Fuzzy control calculation theory, show us the
advancement of the measured circuit branch by numerical value, which reflect
the superiority of artificial intelligence sufficiently. Correctly detect the position
of the ground point each time.

This equipment take system safety as primary premise uses reliable low

frequency signal method to test according the highest requirements of industry
standard, and put into practice for test on site, no effects to system.

The DC system of power plant and transformer substation is the power

supply for control, protect, signal and auto equipment, the safe continuous
running is very important to generate and supply power. The DC system is
overhead ungrounded system, it will induce the mentioned device wrong or
failure to act if there was two points grounded. So correctly and fast to detect
the ground contact, clearing of the ground fault meanwhile ensure the DC
system normally supply power, to avoid the damage caused by two points
grounded.

This device applies to detect the accurate ground point position of power

plant, transformer substation DC system. Accuracy up to 100%.

This device with the bellowing advantages compared with the same type

devices:

1. Easy to use, customers can directly operate only need turn on the

power switch.

2. Safe and reliable, do not need power off the charger or other power

source, without effects to DC system.

3. Applies to various voltage class, DC system V, 110V, 48V, 24V.

Summary of Contents for PDF1000

Page 1: ...You can find the changes in the appendix Sorry for the inconvenience If you have further questions welcome to contact with our service department The input output terminals and the test column may br...

Page 2: ...refully to avoid body injury and prevent the product or other relevant subassembly to damage In order to avoid possible danger this product can only be used within the prescribed scope Only qualified...

Page 3: ...t Before connecting please read the instruction manual to acquire information about the ratings Do Not Operate without Covers Do not operate this product when covers or panels removed Use Proper Fuse...

Page 4: ...Security Terms Warning indicates that death or severe personal injury may result if proper precautions are not taken Caution indicates that property damage may result if proper precautions are not tak...

Page 5: ...5 Contents I Overview 6 II Principle 7 III Specifications 8 IV Structure and Function of Instrument 9 V Notes 12 Appendix 1 structural representation 14 Appendix 2 brief method introduction 15...

Page 6: ...system The DC system of power plant and transformer substation is the power supply for control protect signal and auto equipment the safe continuous running is very important to generate and supply p...

Page 7: ...ction under no power interruption no effect to system normal work strong anti jamming ability safe and reliable Waveform analysis inject one special cyclical voltage signal between DC bus bar and grou...

Page 8: ...t circuit output current 80mA Output terminal shock resistance capability 400V DC impulse Supply voltage AC220V 10 Voltage frequency 50Hz 5 Single chip Signal sampling analog to digital conversion Sig...

Page 9: ...2 5mA Display of receiver number 0 19 Dimension 210x100x32mm A jaw size 50mm B jaw size 7mm 9mm 3 Complete appliance Measured maximum ground resistance 300k Ground resistance measurement accuracy 0 4...

Page 10: ...cating having normal low frequency voltage output Signal output the port for signal output When using please insert output leads to output signal Access signal generator Insert signal output leads int...

Page 11: ...s for Signal receiver With calipers respectively clamp all main circuit that were associated with fault bus bar and then observe LCD display Use number 0 19 from low to high to indicate insulation val...

Page 12: ...at let the calipers firmly clamp the feeder cables until obtain stable measured data 4 Signal output lead Red lead connects to fault bus bar terminal black lead connects to ground Red plug inserts int...

Page 13: ...ow battery please replace the battery timely to improve measurement accuracy 7 Since the receiver has high sensitivity when testing please do not grasp it let the receiver in quiescent state so as not...

Page 14: ...14 Appendix 1 structural representation...

Page 15: ...generator 3 Insert the plug of the caliper with the input jack of the signal receiver 4 Turn on the power switch of the signal receiver 5 Strangulate the measured circuit using caliper 6 Begin to test...

Page 16: ...16...

Reviews: