background image

www.h-v-c.com

Symptom

Possible causes

Action

The thermal probe's LED is not lit and the 
damper is closed

No power or incorrect supply

Check supply

Thermal probe has been 
tripped or is faulty

Replace thermal probe tripping element, part reference 
‘Belimo ZBAT72’

Actuator faulty or damaged

Replace actuator
See below: 'Actuator removal and replacement procedure'

Damper blades operating in unison but not 
fully opening or closing

Damper motion obstructed by 
debris

Remove debris
Ensure no damage has been caused to damper

Actuator fitted incorrectly

Remove and refit actuator correctly
See below: 'Actuator removal and replacement procedure'
Ensure no damage has been caused to damper

Damper seized

Lubrication required
See below: 'Lubrication procedure'

Mechanical failure

Contact HVC

Damper blade/s loose and not synchronised

Mechanical failure

Contact HVC

Damper is noisy or judders during operation

Lack of maintenance

Lubrication required
See below: 'Lubrication procedure'

Multiple section unit only

The thermal probe's LED is lit but the 
dampers are closed

Relay box fault

Contact HVC

Multiple section unit only

Damper sections not synchronised 
(e.g. one section closed, one section open)

Installation guide: NCA Series 700 motorised leakage rated fire damper

Operation and maintenance manual
Page 2 of 2 - Issue A - 27/05/2020

Actuator removal and replacement procedure

1.  Isolate and disconnect existing actuator from power supply (or 

multiple fire damper relay box), actuator will spring closed. 

2.  Remove actuator from damper (4 qty M6 bolts), retain bolts. 

3.  If the unit is a single section, remove thermal probe from 

ductwork (2 qty screws). If unit is a multiple section do not 
remove the thermal probe. 

4.  Ensure the new actuator is in its closed position by inserting 

the winding handle (supplied) and relieving the factory set 
spring tension. 

5.  Ensure the damper is still in its closed position.

6.  With the side labelled ‘R’ of the actuator facing away from the 

damper (the ‘L’ side towards the damper), slide the actuator 
onto the 12mm square spindle. 

7.  Using the retained M6 bolts fit the new actuator to the damper, 

and the thermal probe to ductwork if one was previously 
removed. 

8.  Connect the new actuator to an appropriate power supply (or 

multiple fire damper relay box), allow the damper to open and 
then conduct a cycle test as per steps 9 and 10 of the periodic 
maintenance procedure.

Troubleshooting

Additional procedures

Lubrication procedure

1.  Remove access door/s to access the inside of ductwork and 

damper blades

2.  Clean damper if required following step 7 of the periodic 

maintenance procedure. 

3.  Depress the stainless steel side seals, and apply a small 

amount of light oil (WD40 spray grease recommended) directly 
into the blade axle bushes. 

4.  If required a light application of oil can be made to the blade 

ends and stainless steel side, top and bottom seals.

5.  Remove any excess oil with a cloth. 

6.  Conduct a cycle test as per steps 9 and 10 of the periodic 

maintenance procedure and observe whether the operation 
has improved. Several reapplications/cycles may be required 
to permit the lubricant to reach all required areas. 

Contact HVC if the above does not solve your problem. 

Periodic maintenance procedure overleaf →

Reviews: