background image

www.h-v-c.com

Operation and maintenance manual

NCA Series 700 motorised leakage rated fire damper

Regular inspection and maintenance of fire dampers is essential to 
ensure they remain in good working condition. It is the system owner’s 
responsibility to ensure this is carried out. 

In accordance with EN 15650:2010 fire damper maintenance routines, 
such as that given below, must be carried out at intervals not exceeding 6 
months. 

Some automatic systems may allow more frequent testing (48 hours or 
less) and this may be required by national regulation. 

Installation guide: NCA Series 700 motorised leakage rated fire damper

Operation and maintenance manual
Page 1 of 2 - Issue A - 27/05/2020

Damper type:

NCA Series 700 motorised leakage rated fire damper

Thermal probe rated temperature:

72°C

Damper reference (if applicable):

Damper serial number (see CE label):

Damper location (within site):

Date of inspection:

Step Operation

Notes

Yes/No

1

Is the thermal probe LED lit?

Fitted to ductwork near the damper, this indicates the damper is powered 
open (its normal working state)

2

Are the actuator/s, thermal probe (and fire 
damper relay box if present) secure?

Check these are secure and that all fixings are present and tight 
(4 qty M6 bolts on actuator, 2 qty screws on probe)

3

Is all wiring undamaged?

Actuators are not user servicable
If damaged the actuator must be replaced

4

Remove access door/s to access the inside of 
ductwork and damper blades

Both sides of the damper blades should be easily accessible.

N/A

5

Are all damper blades in the fully open 
position and secure?

All damper blades should be in the fully open position. 
Gently try to move each blade by hand, none should rotate.

6

Are the damper blades unobstructed?

Ensure there is nothing present which is obstructing or could obstruct the 
damper blades operating

7

Is the damper clean and free from damage 
and corrosion?

Use a damp cloth, brush or vacuum cleaner to remove any dirt and debris. 
Pay close attention to blade ends and stainless steel seals
If damaged or corroded dampers must be replaced

9

Does the damper close correctly, quietly and 
smoothly?

Depress the 'TEST' button on the thermal probe and visually confirm the 
damper closes correctly in around 16 seconds.

10

Does the damper open correctly, quietly and 
smoothly?

Release the 'TEST' button on the thermal probe and visually confirm the 
damper opens correctly in under 120 seconds. 

11

Do you have any concerns about the 
installation?

Is there anything that does not look correct, do you have any doubts etc.?

12

Refit access door/s securely

N/A

N/A

Danger!
Risk of electric shock

•   Do not touch any live electrical components.
•   Only qualified electricians should work on electrical 
 

equipment.

•   Switch off the power supply before working on any 
 

electrical equipment.

Caution
Risk of entrapment in mechanism

•   During maintenance dampers should remain powered 
 

open and could close while being inspected/cleaned.

•   Never put hands or arms through damper blades 
 

during maintenance.

Troubleshooting overleaf →

Periodic maintenance procedure

If any of questions 1 - 10 is answered ‘no’, or if the answer to 
question 11 is ‘yes’, please see troubleshooting overleaf. 

Reviews:

Related manuals for NCA 700 Series