HVAC Partners R2A3 Installation Instructions Manual Download Page 4

INSTALLATION INSTRUCTIONS

R

22 Split System Air Conditioner

4

421 01 5203 02

Specifications subject to change without notice.

B. REFRIGERANT LINE SETS

The refrigerant line set must be properly sized to assure

maximum efficiency and proper oil circulation.

Refer to Product Specifications and Long Line

Applications Guideline for line set sizing

.

NOTE:

 Total line set length must not exceed 200 feet

(61m).
A crankcase heater must be used when the refrigerant

line length exceeds 80 feet (24.4m).
If outdoor unit is more than 10 feet (3m) higher than the

indoor coil, refer to the Long Line Applications Guideline

manual for instructions.
When the outdoor unit is higher than the indoor coil, the

vertical separation must not exceed 100 feet (30m).
When the outdoor unit is lower than the indoor coil, the

vertical separation must not exceed 50 feet (15.2m).
If it is necessary to add refrigerant line in the field, use

dehydrated or dry, sealed, deoxidized, copper

refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing

until connections are ready to be made.
Be extra careful when bending refrigeration tubing.

Tubing can “kink” easily, and if this occurs, the entire

length of tubing must be replaced.

!

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution may result in

improper product operation.
Do not leave system open to atmosphere any

longer than absolutely required for installation.

Internal system components 

 especially

refrigerant oils 

 are extremely susceptible to

moisture contamination. Keep ends of tubing

sealed during installation until the last possible

moment.

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD
Failure to follow this warning could result in

personal injury or death.
Relieve pressure and recover all refrigerant before

system repair or final unit disposal. Use all service

ports and open all flow

control devices, including

solenoid valves.
Federal regulations require that you do not vent

refrigerant to the atmosphere. Recover during

system repair or final unit disposal.

C. ROUTING AND SUSPENDING REFRIGERANT

LINES

Run refrigerant lines as straight and direct as possible,

avoiding unnecessary bends and turns. Always insulate

the entire suction line. Both lines should be insulated

when routed through an attic or when routed through an

underground raceway.
When routing refrigerant lines through a foundation or

wall, do not allow refrigerant lines to come in direct

contact with the building structure.
Make openings large enough so that lines can be

wrapped with extra insulation. Fill all gaps with RTV caulk.

This will prevent noise transmission between the tubing

and the foundation or wall.
Along floor or ceiling joists, suspend refrigerant lines so

that they do not contact the building structure, water

pipes, or ductwork. Use insulated or suspension type

hangers. Metal straps must be at least 1” (25mm) wide to

avoid cutting into the tube insulation. Keep the liquid and

suction lines separate. Refer to Figure 4.

!

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution may result in

improper product operation.
Do not bury more than 36” (1m) of line set

underground. Refrigerant may migrate to cooler

buried section during extended periods of unit

shut

down, causing refrigerant slugging and

possible compressor damage at start

up.

If ANY section of the line set is buried

underground, provide a minimum 6” (152mm)

vertical rise at the service valve.

D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT

Proper oil return to the compressor should be maintained

with suction gas velocity. If velocities drop below 1500

fpm (feet per minute), oil return will be decreased. To

maintain suction gas velocity, do not upsize vertical

suction risers.

E. LIQUID LINE FILTER

DRIER

NOTE:

 It is required that an approved filter drier (XH-6

with 25% activated alumina/75% molecular sieve

desiccants) be installed in the liquid line due to the POE

oil.
Leave the plugs in the tube ends until the filter

drier is

installed. The optimal location for the filter

drier is close

to the indoor coil. Install the filter

drier with the arrow

pointing towards the indoor coil. Refer to Figure 5.

Summary of Contents for R2A3

Page 1: ...used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combinatio...

Page 2: ...to CLEARANCES section of this document Roof top installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise vibration dampening NOTE Roof...

Page 3: ...HES Check to see that the proper system components are in place especially the indoor coil R 22 outdoor units can only be used with R 22 specific indoor coils If there is a refrigerant mis match consu...

Page 4: ...refrigerant to the atmosphere Recover during system repair or final unit disposal C ROUTING AND SUSPENDING REFRIGERANT LINES Run refrigerant lines as straight and direct as possible avoiding unnecessa...

Page 5: ...EFORE brazing This helps prevent overheating and damage to valve seals refer to Figure 6 Replace valve core when brazing is completed Figure 6 Service Valve VALVE CORE SERVICE VALVE WARNING FIRE HAZAR...

Page 6: ...uum Gauge Response and System Conditions 500 MINUTES 0 1 2 4 6 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 2000 MICRONS 2500 3000 3500 4000 4500 5000 3 7 5 Triple Evacuation Method...

Page 7: ...r to unit rating plate for minimum circuit ampacity and circuit protection requirements Grounding Permanently ground unit in accordance with the National Electrical Code and local codes or ordinances...

Page 8: ...l charge 3m x 17g 51g additional charge This outdoor unit is designed for use only with indoor coils that utilize a TXV refrigerant metering device With an indoor TXV use the subcooling method to make...

Page 9: ...wer motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipped with a time delay relay circuit the blower...

Reviews: