HVAC Partners EHC09AKCN Installation Instructions Manual Download Page 4

482 01 2231 02

4

Specifications are subject  to change without notice

and 30kW heaters, the third stage relay board jumper is cut at

factory. This provides an eight (8) second delay after first stage

relay closes.

Figure 4

Bezel Installation

A03069

Installation of Window Bezel for Circuit Breaker Model Heater

B. Power Connections
NOTE:

 Heater supply circuit wire size and overcurrent protection

must comply with National Electrical Code (NEC) and UL branch

circuit requirements. (See Table 3) Wires and overcurrent

protection, integral to the heater, are not required to meet branch

circuit requirements. Internal circuit protection of 60 amps

(maximum) is acceptable.
1. Unprotected heaters: (See Figures 6, 10, and 11)
a. The 9kW single phase and 15kW three phase heaters can be

wired for single supply circuit only. Supply circuit connects to

heater pigtail leads.

b. The 9kW single phase heaters can use a separate field

installed, factory

authorized disconnect kit which installs in fan

coil.

NOTE: 

Refer to wiring label for component locations.

c. The 9kW heater is factory wired for single supply circuit, single

phase. To convert heater to single supply circuit, three phase:
(1.) Disconnect blue wire from relay 1 terminal 6. Cut, strip, and

connect to field wire L3.

(2.) Disconnect yellow wire from relay 3 terminal 6 and connect

to relay 1 terminal 6.

(3.) Disconnect blue wire from relay 3, terminal 2, and connect

to relay 3 terminal 6.

2. Circuit breaker heaters: (See Figures 7 and 9)
     The 15kW and 20kW heaters can be wired for dual

supply circuits

only.

3. Fused heaters: (See Figures 8, 12, 13, and 14)
a. The 15kW and 20kW heaters can be wired for single or dual

supply circuits. Single supply circuit wiring requires a factory

authorized, single

point adapter kit.

b. The 24kW and 30kW heaters can be wired for single or multiple

supply circuits. Heaters are factory wired for single circuit three

phase. To convert heaters to single circuit single phase, discon-

nect yellow lead from L3 and connect to L1. Disconnect black

lead from L3 and connect to L2. To convert heaters to multiple

supply circuit single phase, remove and discard leads between

single circuit terminal block and fuse block. Remove and discard

single circuit terminal block. Attach L1 through L6 power leads

as indicated on label next to fuse block.

C. Ground Connections

ELECTRICAL SHOCK.
Failure to follow this warning could result in property

damage and/or death.
According to NEC, ANSI/NFPA 70, and local codes,

cabinet must have an uninterrupted or unbroken ground

to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing

electrical codes. (See Ground/Conduit Note below.)

!

WARNING

NOTE: 

Use UL

listed conduit and conduit connector for connecting

supply wire(s) to unit to obtain proper grounding. If conduit

connection uses reducing washers, a separate ground wire must be

used. Grounding may also be accomplished by using grounding

lugs provided in control box.

1. For unprotected or single circuit heaters, 1 equipment ground

connection is provided on fan coil unit. (See Figure 1 or 2)

2. For 15kW and 20kW circuit breaker heaters, an additional

ground lug is provided on circuit breaker mounting bracket for dual

circuit grounding. (See Figure 3)

3. For 15kW and 20kW fused heaters, an additional ground lug is

provided on fuse mounting bracket for dual circuit grounding. (See

Figure 2)

4. For 24kW and 30kW fused heaters, two (2) additional ground

lugs are provided for single phase, multi circuit wiring. (See Figure

1)

D. FAN SPEED SELECTION
FCM

The FCM fan coil with the Observer Wall Control will automatically

select the appropriate airflow for the selected heater size. Refer to

airflow/CFM tables for airflow delivery.

CONVERSION OF CIRCUIT BREAKER FOR DOWNFLOW

APPLICATIONS

1. Tag and disconnect factory wiring from terminals on circuit

breaker(s).

2. Pull white plastic release tab on the bottom of circuit breaker

straight out to release circuit breaker from bracket. (See Figure 16)

3. Remove quick connect adapters from factory side of breaker(s).

Reinstall adapters on other end of breakers(s). Be sure adapter is

located between lug screw and plate. Torque lug screw to 30

in

.lb.

4. Rotate breaker 180 degrees from its original position and reinstall

in bracket. Slide breaker slot into sheet metal tab and snap breaker

into place. Make sure both tabs engage breaker. Reconnect wiring

on opposite end. Make sure wires are positioned as before.

5. Remount circuit breaker bracket into unit so that the switch will be

in UP position when ON.

ATTACH WIRING DIAGRAM AND RATING LABEL

Attach heater rating label included with kit over existing electrical

information label located on front access panel of fan coil. (See

Figure 17) If kit contains multiple rating labels, ensure correct label

is applied (check phase and supply circuits).

VERIFY INSTALLATION

After completion of heater installation, check wiring to ensure

tightness and that proper connections and routings have been

made. Ensure all electrical covers are in place and proper labels

have been applied. Reinstall blower access panel before turning

unit power on.

Summary of Contents for EHC09AKCN

Page 1: ... local codes with National Electrical Code ANSI NFPA 70 1996 or current edition The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments Shut OFF electric power at unit disconnect and or service panel before beginning the following proce dures WARNING USE EHC heater kits ar...

Page 2: ...ters and certified single point wiring kit 15kW 20kW are not recommended for specific heat pump applications see AIRFLOW DELIVERY CFM HEAT PUMP MINIMUM CFM WHEN USING ELECTRIC HEAT CFM FCM Model Size Outdoor Unit Size Heater Size kW 9 15 20 24 30 24 18 625 24 725 875 30 875 875 1040 36 970 970 1040 36 24 875 30 875 1100 1150 36 975 1100 1225 42 1125 1125 1225 48 30 875 875 1150 36 975 1100 1225 42...

Page 3: ...on must be made between plug and receptacle Plug will interlock with receptacle when properly seated Harness contains both 24V control and high voltage wiring Blower power is provided through heater harness NOTE Units with or without electric heaters require a minimum CFM Refer to unit wiring label to ensure the fan speed selected with electric heaters is equal to or greater than the minimum fan s...

Page 4: ...nterrupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes See Ground Conduit Note below WARNING NOTE Use UL listed conduit and conduit connector for connecting supply wire s to unit to obtain proper grounding If conduit connection uses reducing ...

Page 5: ...notice Figure 5 Connection of Transformer 230 C 208 BRN RED YEL BLK SECONDARY PRIMARY A94067 Figure 6 9 kW Non fused Heaters Figure 7 15 and 20 kW Fused Heaters Figure 8 15 and 20 kW Circuit Breakers Figure 9 lug 15 kW 3 Phase Heater Figure 10 24 and 30 kW Heaters ...

Page 6: ...01 2231 02 6 Specifications are subject to change without notice Figure 11 24 and 30 kW Heaters Figure 12 24 and 30 kW Heaters Figure 13 Conversion of Circuit Breaker Figure 14 Heater Rating Label Location ...

Page 7: ...3 24 18 0 3 Fuse 50 1 55 4 71 2 77 8 4 4 8 8 80 80 94 95 24 18 0 1 Fuse 86 7 95 5 116 9 127 9 1 1 6 6 125 150 115 116 EHC30AHCF3 30 22 5 3 Fuse 62 6 69 2 86 8 95 0 3 3 8 8 90 100 97 98 30 22 5 1 Fuse 109 0 120 0 144 8 158 5 0 00 6 6 150 175 117 150 FIELD MULTIPOINT WIRING OR 24 AND 30 KW SINGLE PHASE Heater Model Heater kW P H A S E Heater Amps 208 230V Minimum Circuit Ampacity 208 230V k Minimum ...

Page 8: ...482 01 2231 02 8 Specifications are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC09AKCN Field Convertible to three phase N NON FUSED EHC15AKF B F FUSED B CIRCUIT BREAKER ...

Page 9: ...482 01 2231 02 9 Specifications are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC20AKF B F FUSED B CIRCUIT BREAKER EHC25AHCF EHC30AHCF Shipped three phase see below F FUSED ...

Page 10: ...cations are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC25AHCF EHC30AHCF Field Converted to single phase see below F FUSED Copyright 2015 International Comfort Products Lewisburg Tennessee 37091 USA ...

Reviews: