INSTALLATION  INSTRUCTIONS

ELECTRIC HEAT ACCESSORY

EHC09AKCN, EHC15AKF, EHC15AKB, EHC20AKF, EHC20AKB,

EHC25AHCF, EHC30AHCF

DANGER, WARNING, CAUTION, and NOTE

The signal words

 DANGER, WARNING, CAUTION, 

and

 NOTE

are used to identify levels of hazard seriousness. The signal

word 

DANGER

 is only used on product labels to signify an im-

mediate hazard. The signal words

 WARNING,

 

CAUTION, 

and

NOTE

 will be used on product labels and throughout this manual

and other manuals that may apply to the product.

DANGER

 

 Immediate hazards which 

will

 result in severe per-

sonal injury or death.

WARNING 

 Hazards or unsafe practices which 

could

 result in

severe personal injury or death.

CAUTION 

 Hazards or unsafe practices which

 may

 result in

minor personal injury or product or property damage.

NOTE 

 Used to highlight suggestions which 

will

 result in en-

hanced installation, reliability, or operation.

Signal Words in Manuals

The signal word

 WARNING 

is used throughout this manu-

al in the following manner:

The signal word 

CAUTION 

is used throughout this manu-

al in the following manner:

Signal Words on Product Labeling

Signal words are used in combination with colors and/or

pictures on product labels.

WARNING

Safety Labeling and Signal Words

!

CAUTION

WARNING

!

ELECTRICAL SHOCK HAZARD.

Failure to follow this warning could result in

death and/or personal injury.

Installation or repairs made by unqualified persons

can result in hazards to you and others. Installation

must conform with local building codes or, in the

absence of local codes, with  National  Electrical Code

ANSI/NFPA 70

1996 or current edition.

The information contained in this manual is intended

for use by a qualified service  technician familiar with

safety procedures  and equipped  with the  proper

tools and test instruments.

Shut OFF electric power at unit disconnect and/or

service panel before beginning the following proce-

dures.

!

WARNING

USE

EHC heater kits are designed for use with the Observer

t

Communicating Wall Control and FCM4X communicating fan coil.

When used with the Observer communicating system the electric

heater will be automatically recognized and the airflow will be

configured automatically.

INSTALLATION
INSTALL ELECTRIC HEATER ASSEMBLY
NOTE: 

Ensure heater coils are not deformed or damaged during

heater installation.
1. Make sure power to unit is off.
2. Remove blower access panel of fan coil unit.

UNIT DAMAGE HAZARD.
Failure to follow this caution may result in property

damage.

Before installation of heater, the black and yellow

pigtail leads must be removed from the fan coil board

or wire harness to prevent possible damage to the

product. Electrical power will be provided to the

board through the heater circuit plug.

!

CAUTION

3. Disconnect 2 power wires (black and yellow pigtail leads) from

fan control board or wire harness (if applicable) and discard.

Wires may be part of a plug assembly or attached to terminals

L1 and L2. Remove cooling control plate from fan coil (if

equipped). For 24kW, and 30kW heaters, remove adapter plate.

(See Figure 1)

4. Insert heater assembly into front of fan coil so that element rods

engage holes in rear heat shield.

5. Attach heater control plate to fan coil using 2 screws provided.

For 24kW, and 30kW heater models, attach front of heater to fan

deck using third screw. (See Figure 1)

Summary of Contents for EHC09AKCN

Page 1: ... local codes with National Electrical Code ANSI NFPA 70 1996 or current edition The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments Shut OFF electric power at unit disconnect and or service panel before beginning the following proce dures WARNING USE EHC heater kits ar...

Page 2: ...ters and certified single point wiring kit 15kW 20kW are not recommended for specific heat pump applications see AIRFLOW DELIVERY CFM HEAT PUMP MINIMUM CFM WHEN USING ELECTRIC HEAT CFM FCM Model Size Outdoor Unit Size Heater Size kW 9 15 20 24 30 24 18 625 24 725 875 30 875 875 1040 36 970 970 1040 36 24 875 30 875 1100 1150 36 975 1100 1225 42 1125 1125 1225 48 30 875 875 1150 36 975 1100 1225 42...

Page 3: ...on must be made between plug and receptacle Plug will interlock with receptacle when properly seated Harness contains both 24V control and high voltage wiring Blower power is provided through heater harness NOTE Units with or without electric heaters require a minimum CFM Refer to unit wiring label to ensure the fan speed selected with electric heaters is equal to or greater than the minimum fan s...

Page 4: ...nterrupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes See Ground Conduit Note below WARNING NOTE Use UL listed conduit and conduit connector for connecting supply wire s to unit to obtain proper grounding If conduit connection uses reducing ...

Page 5: ...notice Figure 5 Connection of Transformer 230 C 208 BRN RED YEL BLK SECONDARY PRIMARY A94067 Figure 6 9 kW Non fused Heaters Figure 7 15 and 20 kW Fused Heaters Figure 8 15 and 20 kW Circuit Breakers Figure 9 lug 15 kW 3 Phase Heater Figure 10 24 and 30 kW Heaters ...

Page 6: ...01 2231 02 6 Specifications are subject to change without notice Figure 11 24 and 30 kW Heaters Figure 12 24 and 30 kW Heaters Figure 13 Conversion of Circuit Breaker Figure 14 Heater Rating Label Location ...

Page 7: ...3 24 18 0 3 Fuse 50 1 55 4 71 2 77 8 4 4 8 8 80 80 94 95 24 18 0 1 Fuse 86 7 95 5 116 9 127 9 1 1 6 6 125 150 115 116 EHC30AHCF3 30 22 5 3 Fuse 62 6 69 2 86 8 95 0 3 3 8 8 90 100 97 98 30 22 5 1 Fuse 109 0 120 0 144 8 158 5 0 00 6 6 150 175 117 150 FIELD MULTIPOINT WIRING OR 24 AND 30 KW SINGLE PHASE Heater Model Heater kW P H A S E Heater Amps 208 230V Minimum Circuit Ampacity 208 230V k Minimum ...

Page 8: ...482 01 2231 02 8 Specifications are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC09AKCN Field Convertible to three phase N NON FUSED EHC15AKF B F FUSED B CIRCUIT BREAKER ...

Page 9: ...482 01 2231 02 9 Specifications are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC20AKF B F FUSED B CIRCUIT BREAKER EHC25AHCF EHC30AHCF Shipped three phase see below F FUSED ...

Page 10: ...cations are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC25AHCF EHC30AHCF Field Converted to single phase see below F FUSED Copyright 2015 International Comfort Products Lewisburg Tennessee 37091 USA ...

Reviews: