Cleaning the Turba-shed™
Should the Turba-shed require cleaning, first
shut down the system. Isolate the Turba-shed
and bleed off pressure into an a p p ro v e d
recovery vessel. Remove the top and bottom
sight glasses and the oil supply line. With a
clean, dry, regulated pressure source like
nitrogen, blow out any sludge or dirt. Install
the sight glasses using new O-rings.
Parker Number 2-23,
Compound557
Precision Rubber, Number 023,
Compound 2337
Leak test, evacuate, and charge with fresh oil
(only Suniso 3G or Texaco Capella W F 3 2 ).
Open valves closed to isolate the oil system
and bring the rack back on line.
Replacing Drier and Filter Cores
Shut down the system. Isolate the core to be
replaced and bleed off pressure into an
a p p roved re c o v e ry vessel. Open housing,
replace core and close up. Pressurize, leak test
and bring back into line.