REFRIGERATION DATA

Note:

This data is based on store temperature and

humidity that does not exceed 75°F and 55% R.H.

P4X-E

Discharge Air °F

31

Evaporator °F

24

Unit Sizing °F

22

Btu/hr/ft — Unlit Shelves

P4X-E

‡‡

Parallel

Conventional

U

NLIT

1455

1585

‡‡ Add 10 Btu/hr/ft 

per shelf row

for LED fixtures.

Add 20 Btu/hr/ft 

per shelf row

for fluorescent lamps.

DEFROST DATA

P4X-E

Frequency (hr)

6

Defrost Water (lb/ft/day)

9

(±15% based on case configuration and

product loading.

O

FFTIME

P4X-E

Temp Term °F

48°F

Failsafe Minutes

30

E

LECTRIC OR

G

AS

Not Recommended

Standard Defrost Thermostat

Close on rise: close 48°F – open 33°F

CONVENTIONAL CONTROLS

Low Pressure Backup Control

P4X-E

CI/CO*

17°F / 7°F

Indoor Unit Only, Pressure Defrost

Termination*

48°F

*Use a Temperature Pressure Chart to

determine PSIG conversions.

Estimated Charge (lbs)**

P4X-E

4 ft

1.6

6 ft

2.3

8 ft

3.2

12 ft

4.5

**This is an average for all refrigerant types

actual refrigerant charge may vary by

approximately half a pound.

3 of 9

P/N 0463862_C

HUSSMANN CORPORATION • BRIDGETON, MO  63044-2483 U.S.A. • WWW.HUSSMANN.COM

81 

3

/

4

 

(2077)

31 

5

/

(804)

30 

1

/

4   

(768)

42 

 

(1064)

33 

1

/

(851)

26 

1

/

(665)

Refrigeration 

Outlet

30 

1

/

4

 

(768)

53 

7

/

8

 

 

(1369)

34 

5

/

8

 

(878)

47 

3

/

4

 

(1212)

FAN


L

P4X-E

24 

5

/

8

 

(625)

3 In. 

(77 mm) 

Required 

Air Gap

1

/

(183)

27

 

(686)

11

 

(279)

3

/

4

 

(120)

Electrical 

Case to Case 

Connections

17 

1

/

8  

(436)

12 

1

/

4

 

(311)

Impact  

Excel

P4X-E

All Produce

Multi-deck, 5 Display Levels

Dimensions shown as inches and (mm).

NSF Certification

This merchandiser model is manufactured to meet ANSI/NSF
(National Sanitation Foundation) Standard #7 requirements for
construction, materials & cleanability.

Summary of Contents for P4X-E

Page 1: ...Fan Assembly 1 0058698 Fan Motor Evaporator MO 4410102 0142780 Fan Blade FB 0142780 7W Energy Efficient Fan Assembly 1 0477654 Fan Motor Evaporator MO 4410545 0142780 Fan Blade FB 0142780 Item Part De...

Page 2: ...al legs and center legs NA 29 1 2 750 41 1 2 1054 41 1 2 1054 Distance between edges of center legs NA NA NA 43 7 8 1114 Distance between front legs and splashguard 2 3 4 70 2 3 4 70 2 3 4 70 2 3 4 70...

Page 3: ...Defrost Termination 48 F Use a Temperature Pressure Chart to determine PSIG conversions Estimated Charge lbs P4X E 4 ft 1 6 6 ft 2 3 8 ft 3 2 12 ft 4 5 This is an average for all refrigerant types ac...

Page 4: ...48 120V 60Hz Energy Efficient 0 80 0 96 1 40 2 00 230V 60Hz Energy Efficient 0 50 0 60 0 80 1 10 Maximum Over Current Protection 120V 20 20 20 20 Maximum Over Current Protection 230V 15 15 15 15 Stand...

Page 5: ...isplay Area 3 Sq Ft Ft 4 40 ft2 ft 1 34 m2 m Shelf Area 4 Sq Ft Ft 6 88 ft2 ft 2 10 m2 m 1 Computed using ARI 1200 standard methodology Refrigerated Volume ft3 m3 Unit of Length ft m 2 ARI Refrigerate...

Page 6: ...l Two Row Canopy Optional Three Row Canopy Connector 5 BL W BL W G R BL W B R R R BL BL R BL R R R BL BL R BL R R R B B Orange or Tan Band 3 Row Canopy 5 4 5 5 Connector W B BL BL R BL R R R B 4 ft 6...

Page 7: ...G All components must have mechanical ground and the merchandiser must be grounded CIRCLED NUMBERS PARTS LIST ITEM NUMBERS CASE GROUND Optional Shelf Harness and Light Circuits for Four Rows of Shelve...

Page 8: ...7 7 R BL R BL R BL 7 7 R BL R BL BL BL TYP Shelf Light Plug Receptacle R Red G Green BL Blue B Black W White 120V POWER 120V NEUTRAL FIELD GROUND WARNING All components must have mechanical ground and...

Page 9: ...L R BL R BL R BL 7 7 7 7 7 7 7 R BL 6 B B W W BL R R BL R BL R BL R BL R BL R BL R BL 7 7 7 7 7 7 7 R BL 6 B B W W BL R R Red G Green BL Blue B Black W White 120V POWER 120V NEUTRAL FIELD GROUND WARNI...

Reviews: