Hussmann ISLA IM-FH Installation & Operation Manual Download Page 12

6

 

PN_3034423_C                

U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • www.hussmann.com

9

Plumbing

Waste Outlet and P-TR

AP

The waste outlet is located at the left hand end of these 

fixtures allowing drip piping to be run under the fixture 

lengthwise.
A 1” P-TRAP and threaded adapter are supplied with 

each fixture. The P-TRAP must be installed to prevent 

air leakage and insect entrance into the fixture.

installing Condensate Drain

Poorly or improperly installed condensate drains can 

seriously interfere with the operation of this refrigerator, 

and result in costly maintenance and product losses. 

Please follow the recommendations listed below 

when installing condensate drains to insure a proper 

installation:

1. Never use pipe for condensate drains smaller

than the nominal diameter of the pipe or P-TRAP

supplied with the case.

. When connecting condensate drains, the P-TRAP

must be used as part of the condensate drain

to prevent air leakage or insect entrance. Store

plumbing system floor drains should be at least 14”

off the center of the case to allow use of the P-TRAP

pipe section. Never use two water seals in series in

any one line. Double P-TRAPS in series will cause a

lock and prevent draining.

3. Always provide as much down hill slope (“fall”) as

possible; 1/8” per foot is the preferred minimum.

PVC pipe, when used, must be supported to

maintain the 1/8” pitch and to prevent warping.

4. Avoid long runs of condensate drains. Long runs

make it impossible to provide the “fall” necessary for

good drainage.

5. Provide a suitable air break between the flood rim of

the floor drain and outlet of condensate drain. 1” is

ideal.

6. Prevent condensate drains from freezing:

a. Do not install condensate drains in contact

with non-insulated suction lines. Suction lines

should be insulated with a non absorbent

insulation material such as Armstrong’s

Armaflex.

b. Where condensate drains are located in dead

air spaces (between refrigerators or between

a refrigerator and a wall), provide means to

prevent freezing. The water seal should be

insulated to prevent condensation.

Refrigeration

Refrigerant Type

The standard refrigerant will be R-404A unless otherwise 

specified on the customer order. Check the serial plate 

on the case for information.

Piping

The refrigerant line outlets are piped through the rear 

of the fixture at the left hand end when viewed from the 

back. Insulate suction lines to prevent condensation from 

dripping.

Refrigeration 

L

ines

L

iquid

 

Su

ction

3/8” O.D. 

5/8” O.D.

NOTE:  The standard coil is piped at 5/8” (suction); however, 

the store tie-in may vary depending on the number 

of coils and the draw the case has. Depending on the 

case setup, the connecting point in the store may be 

5/8”, 7/8”, or 11/8”. Refer to the particular case you are 

hooking up.

Refrigerant lines should be sized as shown on the 

refrigeration legend furnished by the store.

install P-TR

APS

 (oil traps) at the base of all suction 

line vertical risers.

Pressure drop

 can rob the system of capacity. To keep 

the pressure drop to a minimum, keep refrigerant line 

run as short as possible, using the minimum number 

of elbows. Where elbows are required, use long radius 

elbows only.

Contro

l Se

ttings

Maintain these parameters to achieve near constant 

product temperatures. Product temperature should be 

measured first thing in the morning, after having been 

refrigerated overnight. For all multiplexing, defrost 

should be time terminated. Loadmaster valves are not 

recommended. The number of defrosts per day should 

never change. The duration of the defrost cycle may be 

adjusted to meet conditions present at your location.

Evaporato

r F

ans

The evaporator fans are located at the center front of 

these merchandisers directly beneath the display pans.
FOR ACCESS TO THE FANS: Remove the right hand 

deck pan as viewed from the front of the case.

Summary of Contents for ISLA IM-FH

Page 1: ...lation Operation Manual Shipped with Technical Data Sheets MANUAL I O ISLA COUNTER CASES ISLA Food Counters IM FR Refrigerated Counters IM FH Hot Counters IM FS Soup Counters P N P N 3034423_C January...

Page 2: ...tions which if not avoided could result in damage to equipment The information contained in this document is the property of Hussmann Corporation and shall not be used in whole or in part without writ...

Page 3: ...r 1 Installation 4 Exterior Loading 4 Bumper Installation 5 Waste Outlet and P Trap 6 Refrigerant Type 6 Piping 6 Control Settings 6 Evaporation Fans 6 Electrical 8 Wiring Color Code 8 Electrical Circ...

Page 4: ...tion within 15 days and retain all packaging The carrier will supply inspection report and required claim forms Shortages Check your shipment for any possible shortages of material If a shortage shoul...

Page 5: ...t safety standards or requirements As clarified by the California State government Proposition 65 can be considered more of a right to know law than a pure product safety law When used as designed Hus...

Page 6: ......

Page 7: ...WELL DATA AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS 240 1 5 1200 240 1 7 5 1800 240 1 10 2400 240 1 12 5 3000 240 1 15 3600 3 2 5 1200 5 0 1200 4 3 7 5 1800 7 5 1800 5 4 10 2400 10 0 2400...

Page 8: ...12 10 2X 25 1 6015 OVERHEAD HEATER DATA AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS 3 94 945 5 65 1355 8 33 2000 10 15 2435 11 75 2820 3 2 3 94 945 4 3 5 65 1355 5 4 5 65 1355 6 5 8 33 200...

Page 9: ...19 0 07 7 5 N A N A N A N A 4 3 2 0 46 36 28 0 26 0 10 10 N A N A N A N A N A 28 0 26 0 10 10 N A N A N A N A 5 4 2 0 46 36 35 0 32 0 12 12 5 N A N A N A N A N A 35 0 32 0 12 12 5 N A N A N A N A 6 5...

Page 10: ...turally designed to support excessive external loading Do not walk on their tops This could cause serious personal injury and damage to the fixture Leveling IMPORTANT it is imperative that the ISLA FO...

Page 11: ...1 Make sure the aluminum channel and end caps are installed Step Use silicone lubricant to help the bumperslide into the channel Step 3 Starting on one end while inserting the bumper push it up again...

Page 12: ...insulation material such as Armstrong s Armaflex b Where condensate drains are located in dead air spaces between refrigerators or between a refrigerator and a wall provide means to prevent freezing...

Page 13: ...al raceway or under the case Thermostatic Expansion Valve Location This device is located on the same side as the refrigeration stub A Sporlan balanced port expansion valve model is furnished as stand...

Page 14: ...igh wattage appliances It should be wired to a dedicated circuit Electrical service Receptacles When a pplicable The receptacles located on the exterior of the merchandiser are intended for scales and...

Page 15: ...ature requirements Critical attention must be given to the heat controls for these hot tables soup bars Both the upper and lower heat controls soup only require lower control must be adjusted to achie...

Page 16: ...1919 Mexico 1 800 890 2900 www hussmann com 13 Startup To fill the well Turn the fill valve to open position Close the drain valve To drain the well Turn the fill valve to the closed position Open th...

Page 17: ...D COUNTERS 14 Operation Turn power switch on Set temperature control to 7 setting Adjust as necessary Adjust overhead heater as necessary Shutting down Turn ON switch off Close fill valve Open drain v...

Page 18: ...hould be cleaned thoroughly and frequently The interior may be cleaned with any domestic soap or detergent based cleaners Sanitizing solutions will not harm the interior bottom however these solutions...

Page 19: ...rate a minimum of 6 hours before stocking with any product 5 When stocking never allow the product to extend beyond the recommended load limit Air discharge and return air flue must be unobstructed at...

Page 20: ...ting The same type of lamp with protective coating must be used if replaced All lamps have the label below ENCAPSULITE SHATTERPROOF COATING SA 10645 Complies with FDA USDA OSHA Regulations for replace...

Page 21: ...des ask for an alternative Also avoid cleaners containing quaternary salts as they also can attack stainless steel cause pitting and rusting 4 Treat your Water Though this is not always practical soft...

Page 22: ...k defrost settings See Technical Specifications section Product load may be over its limits blocking airflow Redistribute product so it does not exceed load level There is a sticker on the inside of t...

Page 23: ...s freezing over Return air is blocked make sure debris is not blocking the intake section Coil close offs are not installed Inspect coil to make sure these parts are on the case Large gap is visible o...

Page 24: ...and call Hatco to replace if necessary Faulty control Check and call Hatco to replace if necessary Losse wiring on heater Check wiring electrical connections Temperature setting Off Increase shelf hea...

Page 25: ...ing equipment caused by liming sediment buildup chemical attack or freezing or Product misuse tampering or misapplication improper installation or application of improper voltage 2 LIMITATION OF REMED...

Page 26: ...___________ ______________________________________________________________________________________________ _______________ _____________________________________________________________________________...

Reviews: