background image

IGIC-CIDM-0508

6

Refrigeration

The  standard  refrigerant  will  be  R-  unless  otherwise 

specified on the customer order. Check the serial plate on 

the case for information.

piping

The  refrigerant  line  outlets  are  located  under  the  case. 

Locate first the electrical box, the outlets are then on the 

same side of the case but at the opposite end. Insulate 

suction lines to prevent condensation drippage.

Refrigeration Lines

Liquid 

Suction

3/8” O.D.

5/8” O.D. 

nOTe:   The standard coil is piped at 

5

/

8

” (suction); however, 

the store tie-in may vary depending on the number of 

coils and the draw the case has. Depending on the case 

setup, the connecting point in the store may be 

5

/

8

”, 

7

/

8

”, 

or 1

1

/

8

”. Refer to the particular case you are hooking up.

Refrigerant  lines  should  be  sized  as  shown  on  the 

refrigeration legend furnished by the store.
Install 

p-TRApS

 (oil traps) at the base of all suction line 

vertical risers.

pressure drop

 can rob the system of capacity. To keep the 

pressure drop to a minimum, keep refrigerant line run as 

short as possible, using the minimum number of elbows. 

Where elbows are required, use long radius elbows only.

Control Settings

See the “Case Specs” section of this guidebook for the 

appropriate settings for your merchandiser. Maintain these 

parameters to achieve near constant product temperatures. 

Product  temperature  should  be  measured  first  thing  in 

the  morning,  after  having  been  refrigerated  overnight. 

For  all  multiplexing,  defrost  should  be  time  terminated. 

Loadmaster valves are not recommended. Defrost times 

should be as directed in the Case Specifications section 

of this guide. The number of defrosts per day should never 

change. The duration of the defrost cycle may be adjusted 

to meet conditions present at your location.

Access to TX valves and Drain Lines

Mechanical -

 Remove product from end of case. Remove 

product  racks.  Remove  refrigeration  and  drain  access 

panels (labeled). TX valve (mechanical only) and drain are 

located under each access panel at end of the case.

electronic - 

The Electronic Expansion valve master and 

slave cylinder(s) are located within the electrical access 

panel(s).

electronic expansion valve (Optional)

A  wide  variety  of  electronic  expansion  valves  and  case 

controllers  can  be  utilized.  Please  refer  to  EEV  and 

controller  manufacturers  information  sheet.  Sensors  for 

electronic expansion valves will be installed on the coil inlet, 

coil outlet, and in the discharge air. (Some supermarkets 

require a 4th sensor in the return air). Case controllers will 

be located in the electrical raceway or under the case.

Thermostatic expansion valve Location

This device is located on the same side as the refrigeration 

stub. A  Sporlan  balanced  port  expansion  valve  model 

is  furnished  as  standard  equipment,  unless  otherwise 

specified by customer.

expansion valve Adjustment

Expansion  valves  must  be  adjusted  to  fully  feed  the 

evaporator.  Before  attempting  any  adjustments,  make 

sure the evaporator is either clear or very lightly covered 

with frost, and that the fixture is within 10°F of its expected 

operating temperature.

Measuring the Operating Superheat

1.   Determine the suction pressure with an accurate 

pressure gauge at the evaporator outlet.

.   From a refrigerant pressure temperature chart, 

determine the saturation temperature at the 

observed suction pressure.

3.   Measure the temperature of the suction gas at the 

thermostatic remote bulb location.

4.   Subtract the saturation temperature obtained in step 

No.  from the temperature measured in step No. 3.

5.   The difference is superheat.

6.   Set the superheat for 5°F - 7°F. 

T-STAT Location

T-STATS are located within the electrical raceway. Refer 

to diagram below.

TIME CLOCK

T-STAT

BALLASTS

Refrigerant Type

Summary of Contents for CHINO CIDM-E

Page 1: ...CIDM E CIDM I p n IGIC CIDM 0508 INSTALLATION OPERATION GUIDE CHINO CIDM E I Rev 0508 Installation Operation Manual...

Page 2: ...ains Information on CIDME CIDMI Refrigerated Self Service Island Display including 4 Crown and 3 Center Modules available as standard refrigerated med temp Shipping Damage All equipment should be thor...

Page 3: ...Plan Views 29 1 2 6 9 19 5 16 6 3 16 2 7 8 11 3 11 16 40 13 16 48 3 16 CIDM ISLAND 3 11 16 CIDME 34 7 8 3 1 16 12 13 16 27 36 33 30 3 8 10 Elec Elec Elec Ref 26 1 8 25 1 8 23 1 16 21 1 8 23 1 8 Ref D...

Page 4: ...hen cases are joined in the field When joining use a carpenters level and shim legs accordingly Case must be raised correctly under legs where support is best to prevent damage to case 1 Check level o...

Page 5: ...and product losses Please follow the recommendations listed below when installing condensate drains to insure a proper installation 1 Never use pipe for condensate drains smaller than the nominal dia...

Page 6: ...Access to TX Valves and Drain Lines Mechanical Remove product from end of case Remove product racks Remove refrigeration and drain access panels labeled TX valve mechanical only and drain are located...

Page 7: ...s provided on the exterior back of these models is intended for computerized scales with a five amp maximum load not for large motors or other high wattage Finishing Touches Plexiglass Joining Instruc...

Page 8: ...V H O will shorten the shelf life of the product Case Cleaning Long life and satisfactory performance of any equipment are dependent upon the care given to it To insure long life proper sanitation an...

Page 9: ...ocated on the case itself CLEANING PRECAUTIONS When cleaning Do not use high pressure water hoses Do not introduce water faster than waste outlet can drain NEVER ONASELF CONTAINED UNIT WITHAN EVAPORAT...

Page 10: ...DM CIDME 4 X3 W0300006 CIDME w OMNISTAT W0300008 CIDMI 3 W0300007 CIDMI 3 w OMNISTAT W0300009 CIDM I R 14 W0300017 CIDM I SC 14 W0300018 CIDM I R Hot Gas 14 W0300019 CIDM I R Hot Gas 10 W0300020 CIDM...

Page 11: ...FAN H4 H2 H3 H1 L2 ZONE SENSOR IS LOCATED BEHIND THE TOP FRONT DISCHARGE AND IS ATTACHED TO THE FRONT CAD SUPPORT STANDARD EVAP SENSOR IS LOCATED ON THE SECOND RUN OF THE COIL COMING AWAY FROM THE CAD...

Page 12: ...OMNI STAT PN952911 230VAC POWER SUPPLY 230 Vac PROD TEMP AIR TEMP L 9 1 2 3 4 5 6 7 8 CONDENSING UNITS COPELAND F9AM A103 CFV 140 1 H P R 22 RLA 9 5 1857W MCC 13 7 LRA 43 3 225 03 0121 1 R CONDENSING...

Page 13: ...T8 SPX30 2 125 03 1072 F25 T8 SPX30 2 125 03 1072 208 240 VAC 60 Hz L1 ZONE EVAP DEF COMM COMP ALARM FAN H4 H2 H3 H1 L2 ZONE SENSOR IS LOCATED BEHIND THE TOP FRONT DISCHARGE AND IS ATTACHED TO THE FRO...

Page 14: ...MCC 13 7 LRA 43 3 225 03 0121 1 R CONDENSING UNIT M M LIGHT CIRCUIT 93A 100W M CRTL PRSR DUAL 225 01 0706B BLK 14 RED 14 WHT 14 WHT 14 RED 14 BLK 14 RED 14 MCA 7 8A MOP 15A SAFETY SWITCH FLOAT SWITCH...

Page 15: ...2 F25 T8 SPX30 2 125 03 1072 F25 T8 SPX30 2 125 03 1072 F25 T8 SPX30 2 125 03 1072 M M M EVAP FAN MOTORS 2 9W CW 125 01 3076 TERMINAL BLOCK 125 01 0295 BLUE WHITE 115 V L1 2 6 L2 L3 208 V 17 5 17 5 24...

Page 16: ...W BROWN BROWN CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE WHITE BLACK BROWN BROWN BROWN BROWN YELLOW YELLOW RED RED BLUE WHITE BLUE WHITE BLUE BLUE BALLAST 125 01 3273 MAGNETE B432PUNVHP A BAL...

Page 17: ...B432PUNVHP A BLUE BLUE BLUE WHITE BLUE WHITE RED RED YELLOW YELLOW BROWN BROWN BROWN BROWN BLACK WHITE F15 T8 SPX30 2 125 03 0007 F15 T8 SPX30 2 125 03 0007 F15 T8 SPX30 2 125 03 0007 F15 T8 SPX30 2 1...

Page 18: ...W BROWN BROWN CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE WHITE BLACK BROWN BROWN BROWN BROWN YELLOW YELLOW RED RED BLUE WHITE BLUE WHITE BLUE BLUE BALLAST 125 01 3273 MAGNETE B432PUNVHP A BAL...

Page 19: ...F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F32T8 48 125 03 1073 F32T8 48 1...

Page 20: ...5 03 1073 M M M 15 AMP FUSE 125 01 3282 FUSE HOLDER 125 01 3283 15 AMP FUSE 125 01 3282 FUSE HOLDER 125 01 3283 BLACK WHITE M FAN MOTORS 4 9W CW 00001212 F15T8 18 125 03 1075 F15T8 18 125 03 1075 F15T...

Page 21: ...18 07 CIDM W0300021 CIDM E R EVAP FAN MOTORS 2 125 01 0615A 6A 49W 120VAC LIGHT SWITCH TOGGLE 125 01 0307 INSIDE PERIMETER LIGHTS 2 125 03 1075 F15 T8 SPX30 OUTSIDE PERIMETER LIGHTS 4 125 03 1071 F17...

Page 22: ...MCA 65A MOP 15A L1 N BLK 14 WHT 14 TAG ORANGE BLK 14 WHT 14 TAG BROWN BALLAST 125 01 3266 FULHAM LH3 120 L INCOMING POWER 120 VAC 60 Hz GFCI DUPLEX 125 01 3178 BLK NOTE FOR GFCI PROTECTION IF MORE THA...

Page 23: ...t after control Switch On or from digital input A4 or A5 4 C 0 199 min 0 0 d6 Block temperature display during defrost 0 no 1 yes C 0 1 flag 1 1 dd Dripping time after defrost F 0 15 min 2 0 d8 Alarm...

Page 24: ...POINT desired temperature value Press the SET button for one second to display the Set Point value After few seconds the set value blinks Press UP or DOWN to increase or decrease the set point value p...

Page 25: ...with normal refrigeration practices Refrigeration piping should be insulated according to Hussmann s recommendations 1 3 A clogged waste outlet blocks refrigeration The installer is responsible for th...

Page 26: ...arge opening c READING It should first be determined that the refrigerator is refrigerating and has operated at least one hour since the end of the last defrost period The thermometer reading should b...

Page 27: ...hese rules a Buy quality products b Receive perishables from transit equipment at the ideal temperature for the particular product c Expedite perishables to the store s storage equipment to avoid unne...

Page 28: ...________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________...

Reviews: