Warm storage temperatures
1. Temperature control not
set properly
1. Reset control
2. Short of refrigerant
2. Leak check - change
drier, evacuate and recharge
3. Cabinet location too warm
3. Relocate cabinet
4. Too much refrigerant
4. Change drier evacuate and
recharge
5. Low voltage, compressor
cycling on overload
5. Check voltage supply
Compressor runs
continuously – product too
cold
1. Defective control
1. Replace
2. Control feeler tube not
installed in well
2. Push control feeler tube
into well
3. Short on refrigerant
3. Leak check change drier
and recharge
Compressor runs
continuously – product too
warm
1. Short on refrigerant
1. Leak check – change
dryers evacuate and recharge
2. Inefficient compressor
2. Replace
LID GASKET REPLACEMENT –
Remove lids
Grasp the bottom of the gasket with the fingers and pull outward
Work the bottom of gasket from the retainer all around the perimeter openings.
Lift up the gasket and remove the phillips head screws holding the retainer in place. Note :
Mark retainer location so when reinstalling the screws, the screw holes will line up.
Lift gasket and retainer from opening and remove gasket.
8