INSTRUCTION MANUAL AIR QUALITY SENSORS GS 4X.00 KNX 
 

HUGO MÜLLER GMBH & CO KG, STURMBÜHLSTR. 145-149, 78054 VS-SCHWENNINGEN

 

 

 

SAFETY INSTRUCTIONS AND BASICS 

 

 

GS 40.00 knx 

 

GS 41.00 knx 

 
 

 

 

 

Technical data  

 

Safety instructions / Intended use 

Power supply: 
Bus current: 

Via  KNX bus voltage 
< 10 mA 

 

 

CAUTION!

  

 

DANGER OF FIRE AND ELECTRIC SHOCK! 

!!!Installation and assembly of electrical equipment must be carried out only by a skilled person!!!

 

Bus system : 

KNX 

 

  

Connect only to suitable supply voltage 

[KNX bus voltage (nominal voltage 29V

)].  

  

Warranty void if housing opened by unauthorized person! 

  

The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if external in fluences 

exceed   certain limits! 

  

Installation and assembly of electrical equipment must be in accordance with national buildin g, electrical and safety codes! 

  Defective devices / sensors have to be put out of service immediately! 
  Observe the regulations and instructions in the ZVEI/ZVEH handbook (building system technology). Especially the professional 

installation of  

the bus lines and the professional installation and start-up of KNX devices must be observed! 

  The device fits for the particular use of the following tasks: monitoring of the air quality in building systems technology (schools, 

offices,   hotels, conference venue etc.), data transfer and regulation via bus system. 

  The device is intended for use in accordance with the defined technical data. 
  Operate the device exclusively in a dry room! 
  The device is not qualified for security relevant tasks such as emergency doors, fire protection equipment, fermenting cellar s etc. 

Sensors: 

CO

2

, relative humidity, temperature, 

atmospheric pressure 

 

Manual operation (GS 41.00 knx): 

Manual adjustment of set-point temperature 
±3° (increment 0.5°) 

 

Measuring range CO2 concentration: 

390–10.000 ppm 

 

Measuring range relative humidity: 

0–100% 

Measuring range temperature: 

0–50°C 

Measuring range atmospheric pressure: 

absolute atmospheric pressure 

 

Permitted ambient temperature : 

-0°…+50°C 

Housing: 

self-extinguishing thermoplastic 

Mounting: 

Wall 

Type of connection : 

KNX bus terminal 

Type of protection : 

IP 20 to DIN EN 60529 

Class of protection: 

III when installed according to regulations 

Source of interference 

Inappropriate use / disposal 

 Operation of GS 41.00 knx 

The measurement results of the device can 
be negatively influenced by external factors. 
Possible sources of interference are:  
■ Draught and air movement: e.g. through 
windows, doors, convection, heating and 
people 
■ Warming and cooling: e.g. sunlight or 
mounting on an outside wall  
■ Heat sources: close to installed electrical 
consumers e.g. dimmers 

■ Vibrations or shocks, which the unites are 
or were subjected to 
■ Pollution due to colors, wallpaper paste, 
dust e.g. at renovation work 
■ Organic solvents or their vapours: e.g. 
detergents 
■ Plasticizers from stickers and packaging: 
e.g. bubble wrap or polystyrene 

 The device is not intended for use of unauthorized constructional 

alterations, repairs and security relevant tasks  

 The device is not intended for use in outdoor areas and wet rooms 

 The device is not qualified for security relevant tasks The controlling of 

the device is only for the observation and regulation of the air quality 

 The inappropriate use of the device can cause damage to property and 

persons 

 The device has to be disposed in an environmentally friendly manner 

according to the current electrical codes! 

Set-point temperature 
manually adjustable 
via touch-area 
(adjustment range 
±3°; increment 0.5°). 
Display with LEDs. 

 

ASSEMBLY 

 

Assembly 

 

 

Disconnect device from power supply for wiring and installation  

      purposes! Check power supply is disconnected!

 

  Attention! You have to check and consider the safety instructions above! 

 This device is suitable for wall mounting or for mounting on a flush-mounting box. 

 The device should not be exposed to dusty environment. 

 Ensure that no dust get inside of this device. 

 After initial startup, the device requires up to 5 minutes until the first correct 

 

measurement is possible 

 

 

STEP 1:

  

Open the device at the bottom and remove the front cover! 

STEP 2:

  

Mount the rear cover to the wall or on a flush-mounting box

 

 

 

 

(see installation note) 

STEP 3:

  

Press the blue „learn button“ to put the device into operation  

 

 

 

(you can do this later at any time!)  

STEP 4:

  

After completing the installation the front cover must be reattached!

 

Installation note: 

For an easy mounting and installation, you can unplug the ribbon cable to remove the front cover completely. (Ribbon cable: logic cable connection between front -cover and back-cover). After mounting / installation => For a proper function of 

the device you have to reconnect in the ribbon cable. 