background image

Page 

1/2 

Rev. 

03/17/21

3483A_NXP2-RL_SPEC

© 2021 Hubbell Control Solutions, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 

701 Millennium Blvd • Greenville, SC 29607 / Tel 864.678.1000 / hubbellcontrolsolutions.com

FEATURES

•  Robust mechanically latching single and double pole relays

•   Electrically rated for 60,000+ operations (30,000+ cycles) at full  

20a load

•   Mechanically rated for 120,000+ operations (60,000+ cycles)

•   Short Circuit Current Rating (SCCR) of 14,000A @ 277VAC

•   Manual override switch (integral to the relay)

•  At-A-Glance ON/OFF relay status indicator

•  5 year limited warranty

 BROCHURE



 DIMENSIONAL DRA

WINGS

 NX DESIGN & APPLIC

ATION GUIDE

NXP2 SERIES

NX LIGHTING CONTROL PANEL RELAYS

DATE:

LOCATION:

TYPE:

PROJECT:

CATALOG #:

RELATED PRODUCTS

 NX Lighting Control Panel -  

NXP2 Series

 NX Panel Relay Channel Barrier

CONSTRUCTION

•  Relay Dimensions

• Single Pole - L:106.5mm x W:24.5mm  

x H:60mm

• Double Pole – L:96mm x W:49.5mm  

x H:60mm

1

MOUNTING

•  Mounts directly to NX Lighting Control Panel 

relay mounting strap

ELECTRICAL

•  Relay Operating Voltages

• Single Pole (p/n NXP2-RL-SP):

• General Use: 20A @ 300VAC
• Tungsten: 2400W @ 120VAC
• (Standard) Ballast: 20A @ 300VAC
• Electronic Ballast: 16A @ 277VAC
• Motor Starting: ½ HP @ 110-125VAC;  

1.5 HP @ 220-277VAC

• Double Pole (p/n NXP2-RL-DP):

• General Use: 20A @ 480VAC
• Tungsten: 2400W @ 120VAC

OPERATING ENVIRONMENT

•   Indoor use only
•   32° to 112°F (0° to 50°C)
•  Relative humidity (non-condensing):  

10% to 90%

CERTIFICATIONS

•  UL Listed
•  CSA Approved

WARRANTY

•  5 year limited
•  See 

HCS Standard Warranty

 for  

additional information

SPECIFICATIONS

ELECTRICAL (CONTINUED)

• Double Pole (p/n NXP2-RL-DP) (Continued):

• (Standard) Ballast: 20A @ 480VAC
• Motor Starting: ½ HP @ 110-125VAC;  

1.5 HP @ 220-277VAC

•  Relay Electrical Ratings

• Rated for minimum 60,000+ operations 

(30,000+ cycles) at full 20A load

• Short Circuit Current Rating (SCCR) of 

14,000A @ 277VAC

• Rated full-life with HID load

•  Relay Mechanical Ratings

• Rated for minimum 120,000+ operations 

(60,000+ cycles)

OPERATON

•   Mechanically  latching
•  Provides at-a-glance indication of ON or OFF 

relay status

•  Includes manual override switch (integral to 

the relay)

Notes:
1

Double pole relays occupy (2) relay spaces.

ORDERING GUIDE

Example:

 NXP2-RL-SP

CATALOG #

NXP2-RL

Model

Type

NXP2-RL

NX Lighting Control Panel V2 Relay

SP

Single Pole - General Use: 20A @ 300VAC; Tungsten: 2400W @ 120VAC; (Standard) Ballast: 20A @ 300VAC; Electronic Ballast: 16A @ 
277VAC; Motor Starting: 

½

HP @ 110-125VAC; 

½

HP @ 220-277VAC

DP

Double Pole - General Use: 20A @ 480VAC; Tungsten: 2400W @ 120VAC; (Standard) Ballast: 20A @ 480VAC; Motor Starting: 

½ 

HP @ 

110-125VAC; 1.5HP @ 220-277VAC

Single Pole Relay

Double Pole Relay

Reviews: