P/N 00912317 FORM NO. K1218 R0916 ECO 7-023-16
Side 2 of 2
OPERATION
•
Caution:
The switch cannot be turned
ON
without
fully inserting an approved plug (see list below). A
plug cannot be inserted or withdrawn unless the
switch is
OFF
. To remove the plug turn the switch to
the
OFF
position and pull back on the locking pin
knob while pulling on the plug.
•
Note:
Switch cannot be operated until the locking pin
has fully engaged the plug.
ROUTINE INTERLOCK VERIFICATION
•
Warning:
Perform this test before energizing the
receptacle.
•
Before inserting the plug verify that the switch can
not
be turned to the
ON
position.
•
Insert the plug, turn the switch to the
ON
position, pull
on the locking pin knob and verify that the plug can
not
be withdrawn
without
turning the switch to the
OFF
position.
•
If the
receptacle
does
not perform
properly
discontinue use immediately!
ELECTRICAL TEST
•
Warning:
Perform this test before energizing the
receptacle.
•
Test continuity of wiring to verify correct polarity,
phasing, and grounding connections.
•
Measure insulation resistance to be sure the system
does not have any shorts or unwanted grounds.
MAINTENANCE
•
Electrical
and
mechanical
inspection
of
all
components must be performed regularly. It is
recommended that an inspection be performed a
minimum of once a year.
•
Inspect all terminals for tightness (
Retorque
).
Discoloration due to excessive heat is an indicator of
possible
problems and
should
be
thoroughly
investigated and repaired as necessary.
•
Inspect grounding and bonding for correct installation
and secure connection (
Retorque
).
•
Warning: Do not modify these devices in any way.
Replace with proper replacement part(s) supplied by
Killark before continuing service. Failure to do so
could cause serious or fatal personal injury and/or
equipment damage.
•
Inspect gaskets for deterioration and replace if
necessary.
•
Clean exterior surfaces making sure nameplates
remain legible.
•
Torque all bolts and screws as described in the
instructions before reusing the device.
•
Inspect receptacle thread used for plug locking ring
for proper lubrication. Apply Killark
“LUBG” type
lubricant or equivalent to thread surfaces as required
to prevent galling between the receptacle and locking
ring threads.
•
In
addition
to
these
required
maintenance
procedures, we recommend an Electrical Preventive
Maintenance Program as described in the National
Fire Protection Association Bulletin NFPA No. 70B.
•
Replacement Parts:
(Cover Only)
VSQ6023-COV
VSQ6034-COV
VSQ6023-S37-COV
VSQ6034-S37-COV
•
Note:
The S37 suffix designates a polarized
receptacle.
FIGURE 1
INTERMATEABILITY FOR PLUGS
Device
Killark Plug
Crouse Hinds Plug
Appleton Plug
VSQ6023
VP6385
APJ6385, NPJ6383, NPJ6384
ACP6023BC
VSQ6034
VP6485
APJ6485, NPJ6483, NPJ6484
ACP6034BC
VSQ6023-S37
VP6385-S37
APJ6385-S4, NPJ6383-S4, NPJ6384-S4
ACP6023BC-P4
VSQ6034-S37
VP6485-S37
APJ6485-S4, NPJ6483-S4, NPJ6484-S4
ACP6034BC-P4
WARNING
Electrical power supply
MUST BE OFF
before and
during installation and maintenance.
DISCONNECT
primary power source and
LOCK OUT
. Installations and
maintenance procedure must be performed by a trained
and competent electrician
WARNING
If any parts of the plug, receptacle, or switch appear to
be missing, broke, or show the signs of damage.
DISCONTINUE USE IMMEDIATELY!