HUBBELL ELECTRICAL PRODUCTS 

A Division of HUBBELL INCORPORATED (Delaware) 
3940 Dr. Martin Luther King Drive 
St. Louis, Missouri  63113 USA 

INSTALLATION, OPERATION & 

MAINTENANCE DATA SHEET 

SERIES  USF JUNCTION BOXES 

Increased Safety Terminal Enclosures For Use In 

Zone Classified Hazardous Locations

 

 

P/N KIL00921445 FORM NO. K1445  R6/18  ECO-2-045-18   
 

 

 

 

Page 1 of 

10

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

* - Suitable For Use In Division Classified Locations Based On 
Equivalency - See North American Certification Ratings Below 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

   

 

General Safety Information:      

 

CAUTION

:

 

Before installing, make sure you are compliant with area classifications, failure to do so may result in bodily injury, death and 
property damage. Do not attempt installation until you are familiar with the following procedures. All installation must comply with 
the applicable Electrical Code. 

Make sure that the circuit is De-energized before starting installation or maintenance.   
Verify that the installation is grounded.  Failure to ground will create electrical shock hazards, which can cause serious injury and or 
death.

 

IMPORTANT: 

  

Please read these instructions carefully before installing or maintaining this equipment. Good electrical practices should be followed 
at all times and this data should be used as a guide only.

 

Technical information, advice and recommendations contained in these documents is based upon information that Killark believes to be reliable. 
All the information and advice contained in these documents is intended for use only by persons having been trained and possessing the requisite 
skill and know-how and to be used by such persons only at their own discretion and risk. The nature of these instructions is informative only and 
does not cover all of the details, variations or combinations in which this equipment may be used, its storage, delivery, installation, check out, safe 
operation and maintenance.  Since conditions of use of the product are outside of the care, custody and control of Killark, the purchaser should 
determine the suitability of the product for his intended use, and assumes all risk and liability whatsoever in connection therewith.

 

                          

SERIES  USF  JUNCTION BOXES   

Increased Safety Terminal Enclosures For Use 

In Zone* Classified Hazardous Locations

 

0518

 

SIRA 14 ATEX 3157 

IECEx SIR 14.0054

 

 

Summary of Contents for Killark USF Series

Page 1: ...or death IMPORTANT Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a...

Page 2: ...ng in accordance with the local jurisdictional electrical code s e A 1 4 20 UNC M6 ground earthing stud is supplied on all Series USF enclosures f To maintian proper IP ratings be sure to follow all m...

Page 3: ...nstalled the user is responsible for ensuring that the protection concept temperature class and relevant IP rating is maintained i All unused conduit openings must be fitted with a certified close up...

Page 4: ...IECEx FTZU 10 0011U 50o C Klemsan Elektrik PUK Screw FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C Klemsan Elektrik PYK Cage clamp FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C ABB ZS Screw LCIE 08ATEX0007...

Page 5: ...must seat fully against each other to provide the proper joint d Apply a light coating of Killark LUBG lubricant to the box flange before closing the cover All cover screws must be installed tightly 2...

Page 6: ...IIC T6 T5 T4 Gb with Ex e terminals only OR Ex ib IIC T6 T5 T4 Gb with Ex ib terminals only Ex tb IIIC T80o C T100o C T130o C Db IP66 OR Ex eb ib IIC T6 T5 T4 Gb with Ex e ib terminals Ex tb IIIC T80o...

Page 7: ...inimum Distance From Center Line to Center Line of Conduit Cable Entries NPT Metric 4 3 1 2 3 M75 2 1 2 M63 2 M50 1 1 2 M40 1 1 4 M32 1 M25 3 4 M20 1 2 M16 IN mm 2 3 4 70 2 1 2 64 2 51 2 51 1 5 8 41 1...

Page 8: ...ed Hazardous Locations P N KIL00921445 FORM NO K1445 R6 18 ECO 2 045 18 Page 8 of 10 FIGURE 1 USF HINGED COVER See Table 6 and 7 below Note The maximum hole size for enclosure depths of 6 153mm throug...

Page 9: ...69 576 17 63 448 25 63 651 23 0 11 5 USF241608 24 610 16 407 8 203 18 69 475 18 69 475 21 63 549 21 63 549 23 0 11 5 USF241610 24 610 16 407 10 254 14 69 373 22 69 576 17 63 448 25 63 651 31 0 15 5 US...

Page 10: ...4 19 2 488 USF241606 11 79 299 19 20 488 5 79 147 11 75 298 35 2 894 11 2 284 USF241608 11 79 299 19 20 488 11 79 299 11 75 298 35 2 894 15 2 386 USF241610 7 79 198 23 20 589 7 79 198 11 75 298 35 2 8...

Reviews: