background image

 

HUBBELL CIRCUIT -LOCK™ 

SAFETY-SHROUD TWIST LOCK

®

 MECHANICAL INTERLOCK 

 

Installation Instructions 

  

Wiring Device-Kellems 
Hubbell Incorporated (Delaware) 
Shelton, CT  06484  
1-800-288-6000                                                                                                                                                                           
www.hubbell-wiring.com 
PD1785  (Page 1)                     06/11 

                                           

 

 

 

 

 

GENERAL INFORMATION 
NOTICE:

  For installation by a qualified electrician in accordance with national and local 

Electrical codes and the following instructions. 

NOTICE:

  Receptacle MUST be installed BEFORE connection to power supply.  30 Amp  

Maximum receptacle rating.  See ratings table and wiring diagrams. 

CAUTION:  Risk of electric shock.  More than one disconnect switch may be required 
 to de-energize  this equipment before servicing.  Disconnect ALL power supplies to 
enclosure before exposing interior. 
NOTICE:

  This enclosure must NOT be used as a junction box for feed-through 

connections. 

NOTICE:

  Separate overcurrent protection must be provided in accordance with 

National Electrical Code® Article 220 or Canadian Electrical Code, Section B, as  
appropriate.  Overcurrent protection MUST NOT exceed the ampere rating of the 
receptacle. [Ref. National Electrical Code®, Part 1, Rule 430-42(c) or Canadian Electrical  
Code®, Subrule 28-602(3)(c)(i)]. 
Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical 
amperes at the voltage rating of the receptacle. 
This enclosure includes a lockout provision: ON-OFF control knob (in the OFF position) 
accepts up to 5/16 inch (8mm) diameter shackle of a suitable padlock.  Lockout device  
to isolate energy from the connected equipment as a method of compliance to OSHA 
Lockout/Tagout Regulation 29 CFR Part 1910.147.  This feature however, does NOT 
isolate the power supplied to the enclosure during internal servicing of the enclosure. 

MOUNTING INSTRUCTIONS 

For Type 4X and Type 12 applications, enclosure must be mounted by means of 
mounting feet.  DO NOT drill, punch, or nail mounting holes through the enclosure. 
Mount the feet to the enclosure using the # 8 x 7/8 inch (22 mm) thread-forming screws  

provided.  Tighten to 18 pound

·

inches (2.2 N

····

m). 

 
Mounting feet will accept up to ¼ inch (6mm) screws (not provided).  Mounting pattern 
is shown in figure. 
 
Remove the four (4) cover mounting screws and remove the cover.  Switch handle must be 
“off” to remove cover. 

 

Conduit Entrance 

This enclosure may be mounted for top, bottom, or back conduit entrances.  NOTE:  Back 
feed is permitted in Type 4X applications ONLY.  Use ONLY Listed/Certified conduit hub 
rated for type 4X and Type 12 applications.  

Top feed:  

Enclosure is supplied ready for top conduit entrance.

  

 

              When using the top feed conduit entrance, drip loops must always be 

                formed as indicated (•).  Use of user-installed conduit entrances above the 
                  switch are not recommended in applications where condensation may be 
                  present in conduit. 

Bottom feed: 

 Remove frame retention screw and retaining clip, remove frame from box,  

                        turn box 180° , replace frame, and replace retaining clip and retention screw.

 

Back feed:      

Drill or punch a 1.109 inch (28.2mm) diameter hole for ¾ inch TRADE SIZE 

                      conduit hub in the desired conduit entrance location.  Any unused conduit 

entrance holes must be sealed with Listed/Certified closure plug rated                                                                              
Type 4X

 

Install the conduit hub.  Be sure that the O-ring is properly seated in its groove.   

 Tighten the conduit hub. 

WIRING INSTRUCTIONS 

Select conductors having 90°C or higher rated insulation having sufficient ampacity in 
Accordance with the 60°C column of National Elecrical Code® Table 310-16 or Canadian 
Electrical Code Table 2. 

 

SWITCH terminal capacity #

8-12 AWG

; GROUND and NEUTRAL terminal capacity #

8-12 AWG.

 

            

CAUTION:  USE COPPER CONDUCTORS ONLY. 

DO NOT TIN CONDUCTORS. 
Make sure the connected equipment rating does not exceed the rating of this device.  See General Information regarding  
overcurrent protection. 

 
 
 

Summary of Contents for HBL2320SW

Page 1: ...ons enclosure must be mounted by means of mounting feet DO NOT drill punch or nail mounting holes through the enclosure Mount the feet to the enclosure using the 8 x 7 8 inch 22 mm thread forming screws provided Tighten to 18 pound inches 2 2 N m Mounting feet will accept up to inch 6mm screws not provided Mounting pattern is shown in figure Remove the four 4 cover mounting screws and remove the c...

Page 2: ... Use the 5 8 inch 15 9mm stripped end of the conductor Mount the receptacle to the enclosure cover NOTICE Make sure the lock ring arrows are aligned prior to mounting the receptacle Misalignment of the lock ring will prevent insertion of a Safety Shroud Twist Lock plug and will result in improper functioning of the interlock NOTICE Make sure that the lock ring tabs engage the block Install the gas...

Page 3: ...de retenue de Ia platine de montage sortir Ia platine du boîtier pivoter le boîtier de 180 remettre en place la platine Ia pince et Ia vis de retenue Alimentatlon par l arrière Pratiquer une ouverture de 28 2 mm de diamétre CALIBRE DU OMMERCE de 3 4 de pouce à l endroit d entrée de conduit désiré Toute ouverture d arrivée de conduit inutilisée doit être scellée au moyen d un obturateur homologué p...

Page 4: ...egurarse de que el empaque quede debidamente asentado en la ranura Ajustar eI monitor INSTRUCCIONES DE CABLEADO Elegir conductores con una resistencia térmica del aislante de 90 C o más y de capacidad eléctrica suficiente según Ia columna 60 C de Ia tabla 310 16 del National Electrical CodeMR de los E U A Calibres que admiten los bornes del INTERRUPTOR 8 12 AWG Calibres que admiten los bornes de P...

Reviews: