When the assembly is in an ADVANCE system, faults may be automatically detected, transmitted to the
MCU in data messages, and printed out.  Fault messages and possible solutions for their causes are
described in the table below.

Fault Message

Cause and Effect

Possible Solution

Watch-Dog timer

Processor has reset

x

d times

(Where 

x

 is the

number of times the
watchdog timer has
reset the processor.)

Cause

—The watchdog timer has forced the

processor to reset.  This occurs when the Base-16
PCBA reset pins (

J4

) are temporarily shorted or

when the watchdog timer does not receive
regular status pulses from 

U2

 on the Base-16

PCBA.

Effect

—The processor maintains a count of the

number of resets.  If the station is powered down,
the count restarts at zero.  The station still
amplifies incoming pages.  On the 4th reset the 

x

value in the error message resets to 0.

 

Verify that the reset
pins (

J4

) on the Base-

16 PCBA are not
shorted.

 

Replace the Base-16
PCBA.

Supervised Audio
Path

Page Amp

Cause

—The station failed its internal speaker

amplifier health check.

Effect

—The station disables the speaker

amplifier health-check function after the first
failure.  This is a non-restorable fault.

Replace the Base-16 PCBA.

Supervised Audio
Path

Speaker Voice Coil

Cause

—Station isn’t detecting ambient noise at

the speaker or ambient noise is lower than the
configured failure threshold.  This can occur if
there is a fault in the speaker wire or a fault at the
voice coil.  This also can occur if the ambient
noise at the speaker is low, as in a quiet room.

Effect

—The station continues measuring speaker

ambient noise.  When acceptable noise levels are
subsequently measured, a restore message is sent
to the MCU.

 

Verify the speaker wire
is connected and intact.

 

Verify the voice coil is
connected and intact.

 

Verify the Offset Level
adjustment is set
correctly.

 

Replace the Base-16
PCBA.

Polled device

Cause

—This message is output by the MCU

when communication is lost with the station.
This can occur if there is a fault in the page line,
if the station is powered-down, or if there is a
fatal malfunction within the station.

Effect

—The MCU continues to attempt

communication with the station.  A restore
message is output when communications resume.

 

Verify the page line is
connected and intact.

 

Verify the station is
installed correctly.

 

Replace the Base-16
PCBA.

Polled end-of-line
device

Cause

—This message is the same as the “Polled

device” fault, except that the affected station has
been defined as an end-of-line station in the
MCU configuration.

Effect

—When this fault occurs, the red 

EOL

FLT

 LED on the PPI bezel lights.  The LED

extinguishes and a restore message is output
when communication with the station is resumed.

 

Verify that the page line
is connected and intact.

 

Verify that the station is
installed correctly.

 

Replace the station
assembly.

Summary of Contents for Gai-Tronics SmartSeries 751-801

Page 1: ...indirectly to any third party General Information In addition to providing standard Page Party operation the Model 751 801 SmartSeries Speaker Amplifier serves as a control interface to optional devi...

Page 2: ...rtSeries Speaker Amplifier conceals the User Level Adjustment control See Figure 1 for location InternalComponents The assembly contains the following components or subassemblies in the chassis that i...

Page 3: ...the FSK Modem via J1 a 24 pin stacking connector Connector J2 on the Base 16 PCBA connects the speaker transformer for the station s speaker and J3 connects optional external devices Figure 3 Block Di...

Page 4: ...ies speaker amplifier amplifies incoming pages provides speaker supervision and supports other optional features Optional Features The following features are available as options to the standard confi...

Page 5: ...e station as an end of line device for supervision of party line 1 for a station configured either as a Smart Handset Dual Party Select device or a Smart Handset Party Select device Default setting di...

Page 6: ...oved If the fault is in the assembly remove it for repair Note When replacing the assembly perform the following steps when the assembly is part of an ADVANCE system 1 Set the address on the new assem...

Page 7: ...oice Coil Cause Station isn t detecting ambient noise at the speaker or ambient noise is lower than the configured failure threshold This can occur if there is a fault in the speaker wire or a fault a...

Page 8: ...laceable fuses used in the assembly Both are mounted on the Base 16 PCBA as shown in Figure 4 and both limit the amount of current from the 120 V ac source Fuse F1 Ref 4 limits the current to the spea...

Page 9: ...that secure the nameplate 2 Pivot the nameplate counterclockwise exposing the access hole A guide behind the access hole helps direct the screwdriver to the USER ADJ control 3 When you are done with...

Page 10: ...mode for as long as USER ADJ is varying After USER ADJ has remained stable for five seconds the amplifier returns to its normal operating mode VLC Level The VLC Level adjustment sets the speaker ampl...

Page 11: ...HD 1 kHz 12 watts Minimum User Level Adjustment Off 85 to 125 dB SPL SmartVolume Monitor range low gain 62 to 100 dB SPL Offset above ambient User Level Adjustment 0 up to 49 dB Note Offset adjustment...

Page 12: ...elNo Description 12508 002 Amplifier Enclosure Mounting Hardware 12523 001 GAI Tronics Nameplate Kit 12530 001 Transformer Connector Subassembly 12555 001 FSK PCBA Kit 12557 001 Base 16 PCBA Kit 12558...

Page 13: ...be Buyer s sole and exclusive remedy and in no event shall GAI Tronics warranty obligations with respect to services exceed 100 of the total cost of services provided hereunder Warranty Periods Every...

Reviews: