Pub. 42004-563A 

E3 System Controllers 

Page 11 of 16

 

P:\Standard IOMs - Current Release\42004 Instr. Manuals\42004-563A.docx 

01/21 

Input/Output Modules

 

Each I/O module connects to the 

Elemec3

 system controller with a Cat5e cable assembly.  Each I/O 

module contains an input and output RJ45 jack to enable daisy chaining additional I/O modules. 

N

OTE

:

 The Cat5e cables are not Ethernet cables.  Do 

NOT

 connect these cables to a LAN. 

An 

E3 

system controller can supply up to 1.4 amperes to the connected I/O modules.  The installer must 

create a power budget that lists each I/O module and its maximum current draw.  Do not exceed the 1.4-
ampere current limit.  Upon reaching the maximum current draw, add additional modules by providing 
local 24 V dc power to the I/O Module.  Refer to the I/O modules manual for local power connection 
information. 

N

OTE

:

 See the Specifications section for the power requirements of each I/O board. 

Install any of the following types of I/O modules with this controller: 

Table 3.  Input/Output Modules 

Model 

Description 

Inputs / Outputs 

030-02-0095-000 

Elemec3

 Generic I/O 

16 Inputs / 0 Outputs 

030-02-0095-004 

Elemec3 

Generic I/O & Relay 

 1 

16 Inputs / 4 Outputs 

030-02-0095-008 

Elemec3

 Generic I/O & Relay 

 2 

16 Inputs / 8 Outputs 

030-02-0095-00C 

Elemec3

 Generic I/O & Relay 

 3 

16 Inputs / 12 Outputs 

030-02-0095-00G 

Elemec3

 Generic I/O & Relay 

 4 

16 Inputs / 16 Outputs 

030-02-0095-014 

Elemec3

 Generic I/O & Reverse Relay 

 1 

16 Inputs / 4 Outputs 

030-02-0095-018 

Elemec3

 Generic I/O & Reverse Relay 

 2 

16 Inputs / 8 Outputs 

030-02-0095-01C 

Elemec3

 Generic I/O & Reverse Relay 

 3 

16 Inputs / 12 Outputs 

030-02-0095-01G 

Elemec3

 Generic I/O & Reverse Relay 

 4 

16 Inputs / 16 Outputs 

030-02-0096-001 

Elemec3

 Monitored Input Module (MIM)

 

8 Monitored Inputs 

030-02-0097-004  

Elemec3

 Four Output Monitored Relay Modules 

(MRM)

 

4 Monitored Outputs / 
Standard Mount 

030-02-0097-008 

Elemec3

 Eight Output Monitored Relay Modules 

(MRM) 

8 Monitored Outputs / 
Standard Mount 

030-02-0097-014 

Elemec3

 Four Output Monitored Relay Modules 

(MRM)

 

4 Monitored Outputs / 
Reverse Mount 

030-02-0097-018 

Elemec3

 Eight Output Monitored Relay Modules 

(MRM) 

8 Monitored Outputs / 
Reverse Mount 

 

Summary of Contents for GAI-Tronics 013-02-0095-005

Page 1: ...1 System Types 2 Single System Standalone 2 Hot Standby N 1 System 2 Duplicate A B System 2 Important Safety Instructions 3 Front Panel Indicators Control 3 Rear Panel Connections 4 Internal Connecti...

Page 2: ...LEDs 13 Telephone Access 14 Reference Documentation 14 Specifications 14 Electrical 14 System Limitations Maximums 15 Power Amplifier Audio Outputs 15 A B Interlink 15 Audio Outputs Event Record A B...

Page 3: ...ation The Model 013 02 0095 005 and 013 02 0095 006 E3 System Controllers are central components in Elemec3 PAGA public address and general alarm systems They are for use where failsafe operation is i...

Page 4: ...s Connect up to 16 wired access panels for speech broadcasts and manual alarm emergency message activation Additional audio inputs outputs are available to accommodate connections to from ancillary eq...

Page 5: ...s been damaged in any way This includes but is not limited to power supply cord or plug damage exposure to rain moisture or liquid intrusion into the equipment the equipment has been dropped or has su...

Page 6: ...6 P Standard IOMs Current Release 42004 Instr Manuals 42004 563A docx 01 21 Rear Panel Connections Make all system connections at the rear of the E3 system controller see Figure 3 US C LISTED U US C L...

Page 7: ...1 21 Internal Connections All internal connections are plug and socket connections The following figures show the internal components of the two controller models Figure 4 Model 013 02 0095 005 System...

Page 8: ...isconnect power before servicing Do not disconnect the equipment while the circuit is energized Avoid servicing the unit during electrical storms Do not touch uninsulated wires Installation Guidelines...

Page 9: ...ss panel Earth Install an appropriately sized green yellow sheathed conductor between the DC EARTH terminal on the rear of the unit and the telecoms earth bar inside the cabinet see Figure 3 Power Out...

Page 10: ...plifier Connection Generic Amplifier Interface GAI Connect up to 16 generic amplifier interfaces to an E3 system controller The GAI allows connection of alternate amplifiers not specified above for us...

Page 11: ...e audio channel shared by the connected access panels Only one access panel has access to the audio channel at a time When more than one access panel requests access to the audio channel the panel wit...

Page 12: ...the B controller via the A B LINK module per the drawing below see Figure 9 1 Install the IDC ribbon cable between the A B LINK header of the A controller and header CONA of the No 999 02 3003 00X A...

Page 13: ...with this controller Table 3 Input Output Modules Model Description Inputs Outputs 030 02 0095 000 Elemec3 Generic I O 16 Inputs 0 Outputs 030 02 0095 004 Elemec3 Generic I O Relay 1 16 Inputs 4 Outp...

Page 14: ...em interface Install a 20 conductor IDC ribbon cable between the AUX AUDIO 1 port on the controller see Figure 3 and the 20 conductor IDC interface PCBA see Table 4 for the termination pin out informa...

Page 15: ...peration Each E3 system controller receives a custom configuration for its specific application via the Elemec3 Console and Elemec3 Portal applications Please refer to the Elemec3 system manual includ...

Page 16: ...d operation Telephone Access 1 To make a broadcast over the PA system 2 Dial the extension allocated in the IP PBX to the Elemec3 VoIP telephone interface The system transmits a confidence tone to the...

Page 17: ...2 0095 003 only 1 Page Party Interface 1 A B Controller Link 1 USB Port not functional PowerAmplifier AudioOutputs Isolation 500 V RMS Output Level 0 775 V rms at 1 kHz 17 maximum load Bandwidth 200 H...

Page 18: ...ower out 24 V dc out two pin plug with screw terminals Minimum conductor size with ferrule 0 25 mm2 Ethernet LAN RJ45 jack USB Host Port USB USB Type A Receptacle Access Panel Interfaces AP1 4 AP5A 5B...

Page 19: ...of the Contractor s personnel from the work site Re performance of services shall be Buyer s sole and exclusive remedy and in no event shall GAI Tronics warranty obligations with respect to services e...

Reviews: