106.3 Battery Voltage Check

Using a digital volt-ohm meter, check for correct nominal battery voltage between DC Input NEG

and POS wires. Volatge reading should be ±10% of system’s nominal 60Vdc for LG375S, 96Vdc

for LG600S operating voltage. 

107. Final Installation Checklist

IMPORTANT: Before proceeding to the System Start-up Procedure (Section 108) complete

the Final Installation Checklist below.

1.

Ensure the LG cabinet is securely fastened to a wall or other structure.

2.

Ensure that the input circuit breaker in the building service panel serving as the AC disconnect to

the LG system is in the 

OFF

 position.

3.

Check for proper ground connections in the 

LG

 unit cabinet.

4.

Check for any loose wiring connections in the 

LG

 unit cabinet.

5.

Check that correct nominal battery voltage (60Vdc for LG375S, 96Vdc for LG600S) is present in

the 

LG

 unit between the battery’s 

NEG

 and 

POS

 end terminals.

6.

Verify AC Input Voltage Selector Jumpers are installed and in the proper position to accept the AC

input line voltage system voltage configuration.

CAUTION: Failure to install the Voltage Selector Jumpers will prevent system operation.

Installing the Voltage Selector Jumpers in the position that does not match the AC input

line voltage will damage the unit, void the warranty and may cause a dangerous or unsafe

condition.

108. System Start-Up Procedure

IMPORTANT: The LG inverter system is a sophisticated electronic backup power supply.

Care must be taken to follow the steps below in their exact sequence. Failure to do so may

result in possible equipment failure.
CAUTION: Familiarize yourself with the shut down procedure in Section 200.1 before proceed-

ing with the LG system Start Up.

1.

Hold S-1 Pre-charge Switch in the on(up) position for 15 seconds then release.

2.

Place battery circuit breaker (CB-1) in the on position.

3.

Apply utility AC power to the system by turning the branch circuit breaker in the main power panel

to the ON position. Place AC output

 

breakers CB-3 & CB-4 in the on position (if 

equipped

).

4.

Observe the LED Status indicators and verify the following:

A)

AC ON

 indicator (red LED) is illuminated (indicates AC utility power is available to unit).

B)

CHG ON

 indicator (green LED) is illuminated (indicates battery is connected and charger is

operational).

5.

Verify 

Normally-On

 fixtures or switched fixtures (where applicable) are illiminated (local fixture

switch must be in 

ON

 position).

109. Manual System Test

Momentarily push 

TEST

 switch and verify the following:

A) INV ON status indicator (yellow) illuminates (indicates inverter is operational).

B) Normally-On, Normally-Off and Switched fixtures are illuminated (where applicable)

13.

109.1 For LG375S and LG600S

Summary of Contents for DUAL LITE LiteGear LG Series

Page 1: ...Manual For LG Series For 375VA 375W 600VA 600W Large Inverter Power Systems Models LG375S Surface Mounted Version LG600S Surface Mounted Version LG375SI LG600SI Surface Mounted Version w Self Test Su...

Page 2: ...rpose Servicing of this equipment should be performed by qualified service personnel SAVE THESE IMPORTANT SAFETY INSTRUCTIONS The installation and use of this product must comply with all national fed...

Page 3: ...am 120Vac and 277Vac connections AC Input output Wiring Connections to Terminal Block Wiring Diagram Switched Dimming Control 120 277Vac Battery Information Tools Battery installation and Connection W...

Page 4: ...Recharge time Meets UL requirements 96 Hours Battery protection Automatic low battery voltage disconnect and reverse polarity protection Standard batteries Sealed Lead Calcium 7 year life Battery vol...

Page 5: ...s hard to detect because it is colorless ororless and lighter than air 103 Installation Requirements 103 1 Operating Environment Install the LG inverter system in a clean cool dry place with normal ve...

Page 6: ...kouts provided using mounting hard ware not supplied sized appropriately to support the unit weight 105 AC Connections CAUTION A LG inverter system units contain hazardous AC and DC voltages Because o...

Page 7: ...277Vac input connections as well as various modes of output opertion as described in this section Refer to the appropriate wiring diagrams to properly con nect the utility AC power fixtures and exter...

Page 8: ...0 volts Load Operation Adjustable Output AO Option Functionally identical to the Switch Load Operation above but provides four 4 independent settings for each of the four dimmable loads See Wiring Dia...

Page 9: ...R DIMMED CIRCUITS SHOWN Note ONLY 2 OF 4 POSSIBLE SWITCHED OR DIMMED CIRCUITS SHOWN See LiteGear loading table on the next page NOTE Dimming switches are designed for independent settings to allow dif...

Page 10: ...gether or to ground earth Be extremely careful to avoid electric shock and burns caused by contacting battery terminals or shorting terminals during battery installation Do not touch uninsulated batte...

Page 11: ...nd upwards Position batteries in the central locations towards rear of the compartments Carefully install battery retention brackets in each compartment with the supplied hardware Reference below imag...

Page 12: ...12...

Page 13: ...will damage the unit void the warranty and may cause a dangerous or unsafe condition 108 System Start Up Procedure IMPORTANT The LG inverter system is a sophisticated electronic backup power supply C...

Page 14: ...d connected loads B Self testing and a 30 second discharge with a randomized start per UL 924 Sec 30 2 once every 30 days after normal utility power has been supplied for a minimum of 48 hours C Self...

Page 15: ...warranty voided if not routinely recharged NOTE To turn power back on follow the System Start up Procedure outlined in Section 108 Be sure to complete all of the steps to ensure the unit will operate...

Page 16: ...by the Manufacturer will void the UL listing of the system and may cause equipment failure To ensure the superior performance of your LG inverter system and to maintain proper charger operation repla...

Reviews: