background image

 

Page | 11 

 

5. 

  Before working within the UPS cabinet, verify that the UPS has no power applied.   

Before touching the Extended Run Time Battery connector in the UPS, verify that all 
internal battery strings are disconnected (that is, verify that the blue and white 
“powerpole” connectors are NOT mated).  Refer to the UPS manual. Repeat procedures 
3 and 4 to the UPS Extended Run Time Battery connector located in the lower left side 
of the UPS. We recommend that the wires be marked as to which is positive (+) and 
negative (-) to ensure that the wires are not accidentally crossed. See 

Figure 8

 and 

Figure 9

. 

 

 

DANGER

 

 

 

Never connect the positive to the negative.  Severe damage and injury could result.  
Check polarity at the TB3 terminal block. 

 
 
6. 

For –B cabinets, connect the Circuit Breaker Interface per Section 

4. Circuit Breaker 

Interface

. 

 
7. 

Mate the blue connections, blue to blue, and then the white connections, white to white.  
See 

Figure 13

.  Repeat this procedure for the other battery cabinets, if present. 

 
8. 

Reinstall the front inner panel on each battery cabinet using the screws provided. 

 
9. 

After the internal batteries in the UPS are connected, reinstall any panels that were 

removed and close the UPS doors.  Refer to the UPS manual for guidance regarding this 
procedure.  After the UPS cabinet is closed, the battery cabinet breakers may be closed 
and the outer front panels may be replaced on the battery cabinets. 
 
Terminal blocks on the –N version cabinets are disconnected by unplugging the 
“powerpole” connectors in all cabinets.  This requires the removal of the inner panel by 
authorized personnel only. 

 

Table 3 – Terminal Tightening Torques and Wires Sizes 

 

BATTERY INPUT/OUTPUT TERMINAL 

TIGHTENING TORQUE

 

#2/0 - #6 AWG 

120 inch-pounds 

 

GROUND STUD TIGHTENING TORQUE

 

Extended Run Time Battery Cabinet 

100 inch-pounds 

UPS Cabinet 

55 inch-pounds 

 

kVA Rating 

Minimum Input/Output 

Wire Size

 

Minimum Ground 

Wire Size 

10 / 15 

#6 AWG 

#10 AWG 

20 

#4 AWG 

#10 AWG 

30 

#2 AWG 

#8 AWG 

*Wire must be rated 75°C or higher.  Use copper conductors only. 
 
 

Summary of Contents for Dual-Lite Trident TRF Series

Page 1: ...003 2608 Dual Lite Trident TRF Battery Cabinet 10kVA UL924 System 10 30kVA Alternate Runtimes USER MANUAL...

Page 2: ...y the product described herein in order to improve it at any time and without notice For technical assistance contact Dual Lite s Technical Support Center at 1 800 848 6439 Technicians are available d...

Page 3: ...es Battery acid can cause burns to skin and eyes If acid is spilled on skin or in eyes flush acid with fresh water and contact a physician immediately e Equipment should be installed where it will not...

Page 4: ...RNING This product contains Valve Regulated Sealed Acid Batteries These batteries contain lead a neurotoxin and sulfuric acid a corrosive Additionally the energy stored in the batteries can present a...

Page 5: ...Symbols iii Table 2 Model Floor Loadings 3 Table 3 Terminal Tightening Torques and Wires Sizes 11 Table 4 Replacement Batteries and Operating Temperatures 15 Figure 1 The Trident TRF Battery Cabinet 1...

Page 6: ...to prevent loss of valuable electronic information and minimize equipment downtime During brownouts blackouts and other power interruptions batteries provide emergency power to safeguard operation 1...

Page 7: ...fully charged the useful life of the batteries will be reduced if they are subjected to high temperatures The operating temperature range of 15o C to 40o C 5o F to 104o F must not be exceeded for even...

Page 8: ...he equipment 2 Send a copy of the damage claim within 15 days to your service representative 2 2 Floor Loading When planning the installation consider the battery cabinet weight for floor loading The...

Page 9: ...ve the cabinets from the pallet To remove the battery cabinet from the ship pallet 1 Make sure the forklift is rated for the cabinet weight 2 Remove all banding wrapping and foam protectors 3 Remove a...

Page 10: ...ur 4 leveling feet are raised so that they will not touch the floor when the cabinet is placed on the floor 8 Lift the cabinet with a forklift from the rear of the unit one to two inches 1 2 2 5 5cm a...

Page 11: ...Do not tip the cabinet more than 15 degrees from vertical 2 5 Placing the Cabinet Once the cabinet has been rolled into position remove the front panel to access the front leveling feet by pulling the...

Page 12: ...sest to the UPS WARNING TB3 is energized at all times Opening the circuit breakers does not remove power from this terminal block DANGER Only qualified service personnel such as a licensed electrician...

Page 13: ...ver by removing the 10 ten screws mounting it to the enclosure 8 Conduit landing plates are located at the front bottom of the base to accommodate bottom wire entry to the cabinet see Figure 7 Remove...

Page 14: ...CONTROL CABLE ENTRY 1 75 44 5mm X 1 75 44 5mm REAR Figure 7 Bottom View of Cabinet PRODUCTS CO R U1 R3 R2 R1 Q1 J3 J2 J1 F1 D2 D1 BATTERY CIRCUIT BREAKERS B VERSIONS ONLY BATTERY FUSES BATTERY BREAKER...

Page 15: ...battery cabinet to TB1 of the second B battery cabinet Repeat these steps for additional B cabinets Use wire sized per local codes 6 AWG 75 C copper wire minimum to 2 0 AWG maximum When a N version c...

Page 16: ...hite See Figure 13 Repeat this procedure for the other battery cabinets if present 8 Reinstall the front inner panel on each battery cabinet using the screws provided 9 After the internal batteries in...

Page 17: ...of the UPS connect the battery cabinet interface connector TB4 to the UPS per Figure 10 If any additional battery cabinets are N versions no other connections are needed If a Dual Lite maintenance byp...

Page 18: ...ted the batteries must be disconnected by unplugging the cables to the battery trays If it is necessary to remove the cables from the batteries the connections should be marked in a way that no confus...

Page 19: ...o not take away the external support until the extension limit tabs on the upper sides of the battery tray are inserted past the notches on the upper edge of the battery shelf see Figure 12 Always ins...

Page 20: ...rrosive Additionally the energy stored in the batteries can present a shock hazard and a burn hazard Batteries should be serviced by trained personnel Appropriate safety precautions must be observed i...

Page 21: ...Page 16 Figure 13 Cabinet Schematic...

Page 22: ...Page 17 Notes...

Reviews: