background image

RED

BATTERY

BL
AC
K

BL
AC
K

CHA RGER

BOARD

 

Indicator LED TEST

SWITCH

LED 

LAMP

LED 

LAMP

To Remote Lamp Head

-

+

RED

RED

277 VOLT

120 VOLT

CO MM

BLACK

BLACK

WHITE

RED

277 VOLT

120 VOLT

CO MM

BLACK

WHITE

EXIT Light Bar

NOTE: Unused input leads must be properly 

insulated with wire nuts or other approved 

methods

methods.

OPERATION

WIRING DIAGRAM

OPERATION:

EXIT – LED lamps will stay on in AC mode and remain on in the Emergency mode. To perform test, press test switch.
LAMP HEADS –To test the equipment, depress the TEST switch. The charge (LED) indicator will turn OFF and
the emergency lights will illuminate. CAUTION: This equipment is furnished with a sophisticated solid state
transfer switch which will automatically disconnect the emergency lights from the battery if the battery has been
discharged to the end of its useful output.
After test, the automatic charger will return into action, charging the battery and trying to maintain it at a fully
charged state. NOTE: Allow the battery to charge for a minimum of 24 hours after installation or after a power
failure before conducting a 90 minute test.

TESTING

NFPA  101 (Life Safety Code) requires that all emergency lighting equipment be functionally tested every 30 days
for a minimum of 30 seconds and tested annually for a full 90 minute duration. Written records of the testing are to
be kept for examination by the authority having jurisdiction.

TROUBLE SHOOTING:

Does not operate in emergency mode and:
If the charger indicator light is OFF –Check that the circuit breaker for AC supply is ON.
If the charger indicator light is ON –Check that the battery is properly connected.
Emergency lights are dim –Implies battery might not be fully charged. Allow battery to recharge for 24 hours and
then re-test.

MAINTENANCE

:

CAUTION: Always turn OFF AC power to the equipment before servicing. Servicing should be performed only by a 
qualified service technician. Only manufacturer SUPPLIED or APPROVED replacement parts must be used.
BATTERY: The battery supplied with the equipment requires ZERO maintenance. However it should be tested
periodically (see TESTING section) and replaced when it no longer operates the connected fixtures for the
complete duration of a 30 second or 90 minute test. It has a life expectancy of 5-7 years when used in a normal
ambient temperature of 72°F.
LED LAMP BOARD: When re-lamping, only use LED light sources specified. Using other LED light source may
result in transformer damage or unsafe conditions.
OTHER: Clean lenses and replace lamp as, and when, required.

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

IMPORTANT SAFEGUARDS: When using electrical equipment, always adhere to basic safety precautions including the following:

BLACK

Transformer

Transformer

)

BLUE(-)

)

BLUE(- )

)

BLUE(-)

Reviews: