IMPORTANT
1. Luminaire is to be energized in hazardous
locations only after luminaire body has been
secured to Mount (Splice box) and Optics (Globe
or Refractor) as indicated in this document.
2. Verify that luminaire is grounded. Failure to
ground will create electrical shock hazards,
which can cause serious injury and or death.
3. Refer to luminaire nameplate for supply voltage,
ambient, supply wire, and other important data.
All unused conduit opening must be plugged.
Pipe sealant may be applied to threads in plugs
and securely tightened.
4. Great care should be taken when viewing
directly at the LED driven at high currents and
may be hazardous to your eyes
1. DIRECTION FOR INSTALLATIONS
1.
Using the installation images on the left as
your guide, make sure the splice box (mount)
is securely installed. Pull supply wires though
conduit. (Refer to nameplate for proper supply
wire ratings) - Refer to Fig. 1 for details.
2. Luminaire Body is provided with gasket, two
leads and wire nuts. Connect Supply wire leads
from Fig 1 to Luminaire body corresponding
leads using wire nuts. Make sure gasket is
placed as indicated in Fig. 2.
3. Attach Luminaire body on to Splice Box (Mount)
by means of four #8 screws in threaded hole.
Make sure all the wiring is pushed inside the
mount. Now attach the 1/8 in. red silicone rubber
gasket inside luminaire body covering screws
and recessed under threaded area to prevent
from falling out. Optics (globe) is then attached
in the luminaire body tightly over gasket. Refer
to Fig. 3 for details.
4. Guard, if needed, can be threaded on to
luminaire body over optics.
5. Activate supplying circuit to assembled luminaire
to check for its operation.