Hubbel DUAL LITE Spectron Operating Instructions Download Page 2

Operating Instructions (Cont.)

Operation

SPECTRON electronics operation is fully automatic. 
Accidental discharge of the unit battery prior to 
energization is prevented by an AC lockout circuit.  
The unit's green Operating Status LED, located on 
the Spectron display panel, illuminates to indicate 
the presence of AC power.  The unit's red Service 
Alert LED will blink after application of AC power if the 
battery connection is not completed.  During normal 
operation, the unit's charging circuit maintains the 
battery at full capacity and the Spectron Controller 
constantly monitors charger performance. Should 
the terminal voltage vary from design parameter 
values, the unit's red Service Alert LED will blink , 
indicating a malfunction of the battery or charger. 
Upon interruption of normal AC power, or brownout 
condition, the Spectron Controller automatically 
switches the emergency lighting load to the battery. 
Emergency power will be provided for a minimum of 
90 minutes. During emergency operation, the battery 
is protected from deep discharge by a low voltage 
battery disconnect circuit. Upon return of normal AC 
power, a 15 minute retransfer delay holds the unit in 
emergency operation mode allowing utility voltage to 
stabilize prior to reconnection.  The charger will then 
begin a recharge cycle.  A temperature compensated 
float type charger is provided in LT models.  This 
charger is designed to adjust charging voltage with 
changes in ambient temperature to maximize the life 
and performance of the unit's pure-lead type batteries.  
All other Liteforms Series exit signs utilize constant 
current type chargers which require no temperature 
compensation to maintain the unit's Nickel-Cadmium 

batteries.  All chargers will bring the unit battery to 
full capacity within acceptable U.L. time standards. 
The Spectron Controller automatically initiates a one 
minute discharge/diagnostic test every 28 days ± 
3.5 hours and a 30-minute discharge/diagnostic test 
every 6 months ± 1 day. These tests exercise the 
unit’s battery to optimize its capacity and allows the 
SPECTRON Controller to analyze emergency operation 
performance. Any malfunction of the unit’s transfer 
circuit or emergency lamps will cause the red Service 
Alert LED on the unit's display panel to blink.  During 
normal operation, all red Service Alert LED blinking 
indications of unit malfunction remain latched until 
corrected and retested.  A manual test switch allows a 
user programmable 1, 5, 30 or 60-minute diagnostic/
discharge test at any time.  During all automatic and 
user initiated self-tests, the unit's green Operating 
Status LED will blink to indicate a diagnostic cycle in 
process.

Warning:

 This product contains chemicals known to the 

state of California to cause cancer, birth defects, and/or 
other reproductive harm. Thoroughly wash hands after 
installing, handling, cleaning, or otherwise touching this 
product.  

Spectron

®

 

 

Self-Diagnostic Electronics Option

Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com

Copyright

©

 Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A.

 

0601476A  8/08