Hubbel DUAL LITE Spectron Operating Instructions Download Page 1

Manual Tests

Using the unit test switch, users can initiate different 

duration test cycles based on the following table:

Initiating Action 

Test Cycle

Press test switch once 

1 minute

Press test switch twice 

5 minute

Press test switch 3 times 

30 minute

Press test switch 4 times 

60 minute

NOTE:  Pressing test switch at any time after a test cycle has 

begun cancels remainder of test and returns unit to normal 

operation.

Remote Capacity Model Jumper Setting

(

LT_ _ _ 3

 Tandem models only) 

Liteforms Collection Remote Capacity models provide 

sufficient battery capacity to operate one additional 5 

watt remote lighting fixture.  Remote capacity models 

with the Spectron option are shipped from the factory 

with a load sensing jumper provided as shown in position 

"A" of the illustration below.  In this position, Spectron's 

diagnostic circuitry can sense a failure in any of the unit's 

three connected lamps (2 integral and 1 remote).

IMPORTANT

  

If the third (remote) lighting head is not to be connected 

(for the purpose of extended run time or other reasons), 

the load sensing jumper must be reinstalled as shown 

in Position "B" below to prevent a false lamp failure 

indication.  

Operating Instructions

LED Indicators

Two Status LED indicators, one red and one green are 

provided on the control panel of all models equipped 

with the Spectron option.

Red Service Alert LED

Under normal operating 

conditions, the Service 

Alert LED indicator will 

remain off.  In the event the

Spectron Controller detects a malfunction, the Service 

Alert LED will blink at a 1 Hz. rate based on the following 

table:

Service Alert Codes 

Description

One blink ON/pause 

Battery not connected  

Two blinks ON/pause 

Battery fault

Three blinks ON/pause  Charger fault
Four blinks ON/pause  Transfer circuit fault

Five blinks ON/pause 

 

 

 

 

 

Green Operating Status LED

The green Operating Status 

LED serves as both an AC 

power and a self-test 

indicator. During normal 

operation, the Operating 

Status LED will be illuminated indicating the presence 

of AC power.  During all automatic or manual self-test 

cycles, the Operating Status LED will blink at a 1 Hz. 

rate.

Lamp Fault 

LX Exit 

LT Tandem

Exit Legend

 

 

Lamp Head

 

 

Spectron Electronics

All Liteforms Collection models ordered with the 

Spectron (I) option provide:

 Visual indication of AC power status

 Visual Indication of all self-diagnostic test cycles

 Visual indication of unit malfunctions including:

   

• Battery fault

   

• Charger fault

   

• Transfer fault

   

• Lamp fault

 User initiated test cycles of 1, 5, 30 or 60 minutes

 Temperature compensated charger maximizes  

  battery life (LT models)

 15 minute retransfer delay (LT models)

operating status

on = ready
off = ac off
blinking = test in process

LX, LTD Tandem Models Only

Damp Location Listed, 10°C to 40°C (50°F to 104°F) 

Load Jumper Settings

"B"

(2 Lamp Position)

 

"A"

(3 Lamp Position)

Spectron

®

 

 

Self-Diagnostic Electronics Option