Manual Tests
Using the unit test switch, users can initiate different
duration test cycles based on the following table:
Initiating Action
Test Cycle
Press test switch once
1 minute
Press test switch twice
5 minute
Press test switch 3 times
30 minute
Press test switch 4 times
60 minute
NOTE: Pressing test switch at any time after a test cycle has
begun cancels remainder of test and returns unit to normal
operation.
Remote Capacity Model Jumper Setting
(
LT_ _ _ 3
Tandem models only)
Liteforms Collection Remote Capacity models provide
sufficient battery capacity to operate one additional 5
watt remote lighting fixture. Remote capacity models
with the Spectron option are shipped from the factory
with a load sensing jumper provided as shown in position
"A" of the illustration below. In this position, Spectron's
diagnostic circuitry can sense a failure in any of the unit's
three connected lamps (2 integral and 1 remote).
IMPORTANT
If the third (remote) lighting head is not to be connected
(for the purpose of extended run time or other reasons),
the load sensing jumper must be reinstalled as shown
in Position "B" below to prevent a false lamp failure
indication.
Operating Instructions
LED Indicators
Two Status LED indicators, one red and one green are
provided on the control panel of all models equipped
with the Spectron option.
Red Service Alert LED
Under normal operating
conditions, the Service
Alert LED indicator will
remain off. In the event the
Spectron Controller detects a malfunction, the Service
Alert LED will blink at a 1 Hz. rate based on the following
table:
Service Alert Codes
Description
One blink ON/pause
Battery not connected
Two blinks ON/pause
Battery fault
Three blinks ON/pause Charger fault
Four blinks ON/pause Transfer circuit fault
Five blinks ON/pause
Green Operating Status LED
The green Operating Status
LED serves as both an AC
power and a self-test
indicator. During normal
operation, the Operating
Status LED will be illuminated indicating the presence
of AC power. During all automatic or manual self-test
cycles, the Operating Status LED will blink at a 1 Hz.
rate.
Lamp Fault
LX Exit
LT Tandem
Exit Legend
✓
✓
Lamp Head
–
✓
Spectron Electronics
All Liteforms Collection models ordered with the
Spectron (I) option provide:
❑
Visual indication of AC power status
❑
Visual Indication of all self-diagnostic test cycles
❑
Visual indication of unit malfunctions including:
• Battery fault
• Charger fault
• Transfer fault
• Lamp fault
❑
User initiated test cycles of 1, 5, 30 or 60 minutes
❑
Temperature compensated charger maximizes
battery life (LT models)
❑
15 minute retransfer delay (LT models)
operating status
on = ready
off = ac off
blinking = test in process
LX, LTD Tandem Models Only
Damp Location Listed, 10°C to 40°C (50°F to 104°F)
Load Jumper Settings
"B"
(2 Lamp Position)
"A"
(3 Lamp Position)
Spectron
®
Self-Diagnostic Electronics Option