PD2665
(PAGE 2)
05/17
1 Enclosure
2 Mounting foot
3 Drill spots
4 Terminal screws
5 Grounding buss
6 Ground buss mounting screw
7 User installed thru-feed conduit entrance
8 Switch
9 Neutral buss
10 Breather drain (not included)
11 User installed conduit entrance for dual bottom feed
12 Switch release tab. Pull to remove switch
13 Listed/Certified conduit hub rated
Type 4X,12 (One supplied)
14 LINKOSITY Power out
15 Align rib with slot
7. Select the correct wiring diagram. Loosen terminal screws. Insert conductors fully into proper terminals.
8.Tighten terminal screws as follows: SWITCH
terminals: 12‑15 lb•in (1.4‑1.7 N•m); gROuND
and
NEuTRAL
terminals 14.2 lb•in (1,6 N•m).
9.Tighten the grounding buss mounting screw to 4.4‑8.9 lb•in (0.5‑1.0 N•m).
10. Take caution that there are no loose wire strands.
11. Reinstall cover. The handle must be in the “OFF” position. Start each of the four screws by hand to avoid
cross threading. Tighten the four cover screws to 24 lb•in (2.7 N•m). Make sure the sealing O‑rings are in
place under the screw heads.
12. An additional DANgER label (D64558) has been supplied loose with this product as a convenience. Apply
label to the outside of the front cover (see figure M‑11) if the product application does not pose the risk of the
label being removed through cleaning, hose down or any other means.
13. Consult factory for auxiliary contact availability.
14. For all catalog suffix ending in –J or –H refer to selector switch instruction below. See torque setting below.
http://literature.rockwellautomation.com/idc/groups/literature/documents/td/800-td008_-en-p.pdf
http://literature.rockwellautomation.com/idc/groups/literature/documents/td/800-td009_-en-p.pdf
800H selector switch terminal screw torque 6-8 lb-in (0.7-0.9 N-m) of torque. Wire gauge #18-10awg.
WIRING DIAGRAMS
NOTE
: “G” designates ground wire and yellow and green grounding buss.
30 A
600 VAC
1 HP
120 VAC 1Ø
3 HP
200-240 VAC 1Ø
5 HP
480 VAC 1Ø
7.5 HP 200-240 VAC 3Ø
15 HP
480 VAC 3Ø
15 HP
600 VAC 3Ø
NOTICE
: This manual motor con-
troller carries a maximum rating of:
15
A
B
C
Power
in
Power
out
D
B
125 VAC, 1Ø
240 VAC, 1Ø
240 VAC, 1Ø
480 VAC, 1Ø
600 VAC, 1Ø
240 VAC, 3Ø
480 VAC, 3Ø
600 VAC, 3Ø
125/240 VAC, 1Ø
120/208 VAC, 3ØY
240/480 VAC, 3ØY
347/600 VAC, 3ØY
Fig. M-5
Fig. M-3
Fig. M-7
Fig. M-8
Fig. M-9
11
12
4
14
10
Fig. M-6
Fig. M-4
6
8
5
9
14
13