6
TD06118E_0519
3. PSC2080548 (SIDE MOUNT)
a. For single swingarm: Mark the centerline of the top mounting holes 4.0” from the lid lip and 11.0” from
the inside end wall as shown in FIGURE 4.
NOTE: Ensure placement of mounting bracket allows vault lid to close and avoids structural ribs of
vault.
b. For dual swingarm: Repeat step a. on the opposite side wall (see FIGURE 4).
NOTE: Ensure placement of mounting bracket allows vault lid to close, avoids structural ribs of vault,
and avoids second swingarm.
c. For torsion assist cover: No drilling required.
4. Use the mounting bracket as a template to mark (4) hole locations per swingarm mount (see FIGURE 5 and
FIGURE 6)
5. Drill four ø7/16” holes per the layout given in. FIGURE 5 and FIGURE 6.
Lid Lip
FIGURE 4
Side Mount
FIGURE 5
PSC2080547
(END MOUNT)
FIGURE 6
PSC2080548
(SIDE MOUNT)