16.
 
17.

AFTER CONCRETE POUR, SEE FIGURES B, C, D, & E

Locate floor box, remove three screws [7] and remove temporary concrete cover [6].  CAUTION:  Temporary concrete 
covers are intended to keep concrete residue from entering box during pour and are not intended to support loads.  
Replace with permanent flange/cover immediately after concrete has hardened.
Use the wiring channel [8] for feed thru wiring across the box.  Wiring channel areas are given in TABLE 1.  Use care 
not to pinch wiring between the wiring channel and box. Wiring channel [8] must be reinstalled in all finished 
installations.  CAUTION:  ENERGIZING THE ELECTRICAL SYSTEM WITHOUT THE WIRING CHANNEL IN PLACE MAY 
RESULT IN AN ELECTRICAL SHOCK HAZARD!
For feed-thru wiring within a wiring chamber, remove non-metallic dividers [5] as necessary.  
Pull and dress wires.  If grounded metallic conduit is used, connect green grounding lead [9] to grounding terminal on 
receptacle.  For a non-metallic conduit system, pigtail a separate grounding wire to ground both box and receptacle.
Install devices using appropriate floor box mounting plates (FB10MPxx), sold separately.  Use blank plate 
(FB10MPBNK) where no device is installed.   All devices are to be installed in accordance with manufacturer's 
instructions.

11.
 
 
12.
 
 
  
13.  
14.
 
15.

Orient cover support collar [10] as required by removing and reinstalling screws [11].  Lap joint in collar defines the 
hinge location of the cover (SEE FIGURES C  & D).
Install finished flooring to within 1/8 inch [3.2 mm] of cover support collar [10].  FOR CERAMIC TILE - DO NOT GROUT 
BETWEEN THE SUPPORT COLLAR AND TILE.

B

FIGURE

D

FIGURE

TABLE 1

Catalog No.

Minimum depth of pour

Wiring channel areas

Compatible cover series

CFB10G55R, CFB10G55RCR

6.50 inches [165.1 mm]

CFBS1R8CVRxx

(1) 2.4631 in  [1589.1 mm ]

C

FIGURE

6

7

5

9

8

10

11

LAP JOINT
(HINGE SIDE)

10

11

LAP JOINT

(HINGE SIDE)

Summary of Contents for CFB10G55R

Page 1: ...ith all national and local electrical codes communications standards the following instructions and any instructions included with individual devices NOTICE Insure data communications circuits are separated fromlighting power circuits in accordance with the NEC and CE Code requirements Use with CFBS1R8CVRxx series round covers Adjust height of cover support collar flush to just belowthe finished f...

Page 2: ... If grounded metallic conduit is used connect green grounding lead 9 to grounding terminal on receptacle For a non metallic conduit system pigtail a separate grounding wire to ground both box and receptacle Install devices using appropriate floor box mounting plates FB10MPxx sold separately Use blank plate FB10MPBNK where no device is installed All devices are to be installed in accordance with ma...

Page 3: ...nform ment aux codes de l lectricit nationaux et locaux les normes de communication les directives qui suivent et toutes directives incluses avec les dispositifs individuels AVIS S assurer que les circuits de donn es communication sont s par s des circuits d clairage d nergie selon les exigences du Code canadien de l lectricit Utiliser avec les couvercles ronds de la s rie CFBS1R8CVRxx Ajuster la ...

Page 4: ...m tallique mis la terre est utilis connecter le conducteur vert de mise la terre 9 la borne de terre de la prise Pour un conduit non m tallique relier avec un fil s par le fil de MALT pour mettre la terre la bo te et son couvercle Installer les dispositifs en utilisant des plaques de montage FB10MPxx appropri es vendues s par ment et con ues pour les bo tes de plancher Utiliser une plaque pleine F...

Page 5: ...s circuitos de iluminaci n energ a seg n las exigencias de la Norma oficial mexicana NOM 001 SEDE Usar con tapas redondas de serie CFBS1R8CVRxx Ajustar la altura del collar n de soporte de la tapa a ras apenas por debajo del acabado del piso El collar n de soporte de la tapa es ajustable para pisos terminados de 0 pulgada a 25 pulgada 0 0 6 4 mm de espesor Apretar los tornillos de montaje 11 a 10 ...

Page 6: ... a tierra 9 al terminal de conexi n a tierra en el recept culo Para un sistema de tubos no met licos enrollar un cable flexible de conexi n a tierra por separado para conectar a tierra tanto la caja como el recept culo Instalar los dispositivos usando las placas de montaje apropiadas para cajas para piso FB10MPxx vendidas por separado Usar una placa ciega FB10MPBNK donde no haya ning n dispositivo...

Reviews: