I.Technical Characteristics And Parameters

1. Technical Characteristics

The SF6 comprehensive tester integrates the SF6 micro-water meter, the SF6 purity

meter and the SF6 decomposition product analyzer into one, and the functions that were

originally realized with three instruments are concentrated in one instrument. With one

on-site measurement, three indicators can be tested, which greatly saves gas in the

equipment. One measurement saves 2/3 gas consumption, and at the same time reduces

user workload and improves work efficiency.

Fast and gas-saving:

After the start-up into the measurement state, the measurement

time per SF6 gas dew point is about 5 minutes, and the measurement time of SF6 purity

and SF6 decomposition product is about 2 minutes.

Self-locking joint

: It adopts German imported self-locking joint, which is safe and

reliable, and has no air leakage.

Data Storage:

With a large capacity design, up to 200 sets of test data can be stored.

Curve function:

The large screen curve shows the dew point measurement process.

•Clear display:

The LCD screen directly displays dew point, micro water (ppm), SF6

purity, SO2, H2S content ambient temperature, ambient humidity, time and date.

Built-in power supply:

Built-in 4Ah rechargeable lithium battery, enough for 10 hours of

continuous operation.

Summary of Contents for HZSF-641

Page 1: ...HZSF 641 SF6 Gas Analyzer Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ......

Page 3: ...can work continuously for more than 10 hours when fully charged When the integrated tester is left unused for a long time some air will remain in the test pipe and air chamber In the first test the h...

Page 4: ...Contents I Technical Characteristics And Parameters 1 II Panel Instruction 3 III Measurement 4 IV Menu Operation 5 V Remarks 8 VI Packing List 9...

Page 5: ......

Page 6: ...gas saving After the start up into the measurement state the measurement time per SF6 gas dew point is about 5 minutes and the measurement time of SF6 purity and SF6 decomposition product is about 2 m...

Page 7: ...uing Range 0 100ppm Minimum detection 0 1ppm accuracy 0 5 stability 0 100ppm Repeatability 2 SO2 Measuring range 0 100ppm Minimum detection 0 1ppm accuracy 0 5 stability 0 100ppm Repeatability 2 Ambie...

Page 8: ...The angle of the bracket can be adjusted by simultaneously pressing the bracket adjustment buttons on both sides 2 Rear Panel Flow meter LCD Key button Gas inlet Charging indicator Power switch RS232...

Page 9: ...in the upper right corner If the battery level is lower than about 20 please turn off and charge it 4 Start Measuring After the instrument completes the initialization and self checking it automatica...

Page 10: ...ure 1 1 Save The Data In the measurement state press the OK button to enter the function menu press the Up and Down buttons to select the Save Record menu and press the OK button to enter the Save Dat...

Page 11: ...the Up and Down buttons to select the modification time and press the OK button to enter the modification time page At this time the year month day and time can be modified And points the method is a...

Page 12: ...bination Use This Function Is Limited To Dedicated Operation Press the OK button on the measurement interface to enter the function menu Press the Down button once When the second item is selected pre...

Page 13: ...is not in use it should be placed in an aluminum alloy packaging box and placed on the test bench or instrument rack to prevent dust and moisture 4 The instrument is calibrated once a year with standa...

Page 14: ...9 VI Packing List No Item Qty 1 Main engine 1 2 Gas Inlet pipe 1 3 Gas outlet pipe 1 4 Power line 1...

Reviews: