13
Figure 12
Ground network test result interface
The meaning of the measurement results is as follows:
Zx = 75.777mΩ: ground network impedance value
Rx = 75.770mΩ: pure resistance of the ground grid
Φ = 0.769°: vector angle value
X = 0.001Ω: ground network inductance value
L = 0.003mH: ground grid inductance value
Press exit at this time to return to the boot interface (Figure 5). Press print to print out the
result.
Press the store button. The data storage interface appears (Figure 13).
1. Click the data box, a small
Keyboard, fill in the storage serial number.
2. Press the store button, data
After storing, it will return automatically.
3. Press the cancel button to return without saving.