8
definition, you can first select the "10ms before closing" mode, measure the "time-travel
characteristic curve", and then perform corresponding analysis on the curve to obtain the
corresponding speed value.
♦ Output voltage: Set the output operating voltage value according to the needs of the field (it is invalid to
set this item in external trigger mode).
♦ Sensor: The sensor needs to set three parameters: type, quantity and position. Types include
displacement and angle; the number defaults to 1 (some models can be set to 3); the position is the
sensor installation position. If it is a displacement sensor, set it to "A phase", " "B-phase" or "C-phase", if it
is an angle sensor, the default setting is A-phase.
♦ Switch stroke: Enter the total stroke value of the switch when using the angle sensor; enter the marked
stroke value of the sensor when using the angle sensor.
♦ Test time: The total test time is the time of the internal DC power output voltage. This time should meet a.
When doing a single opening and closing test, it should meet the inherent opening and closing time of the
device under test; b. When doing a re-closing test, it should meet the inherent opening and closing time
that is greater than the multiple actions of the device under test Sum of time.
♦ Reclosing time: This item needs to be set during reclosing test. The reclosing and closing time is
counted as T closing and closing, and the reclosing and closing time is counted as T closing and closing.
T opening and closing is the period of time from powering on the opening coil to powering on the closing
coil. T closing is the period of time from powering on the closing coil to powering on the opening coil.
Open—T
open-close
—Close—T
close-open
—Open
When you select the "close-to-open" test mode in the mode selection interface, the "General Mode"
and "Special Mode" options will pop up on the right. The above-mentioned reclosing time can optionally
be performed in the normal mode. If special mode is selected, the time parameters T
open-close
and T
close-open
will be automatically set to 0ms and cannot be changed. Because the working mode at this time is that
when any one of the 12 groups of ports detects a closing signal during the closing process, it immediately
stops the closing command and opens the opening command until the test time is reached.