3

Set value change method

Press the key, the upper row displays SP. Press ▲ or ▼ key to make the lower row

display the required value. Press again or go to standard mode.

Control parameter change method

Press the key for more than 4 seconds, the upper row displays the prompt of the

control parameter, and press the ▲ or ▼ key to make the lower row display the required
value. Continue to press the key, the upper row will display the prompts of each parameter
in turn, press the ▲ or ▼ key to make each control parameter the required value. Press
the key for more than 4 seconds to return to the standard mode. (It will automatically
return to the standard mode after 1 minute without key press)

The function parameters are shown in the table below

Prompt

name

set range

description

Initial value

RESET

-99

99.9

~100

100.0

)℃

RESET

Only used to adjust the static

difference of proportional control

instrument

0

Re

During the auto-tuning process, press the ▲ or ▼ key for 8 seconds and then the AT

light will go out, the auto-tuning will be terminated, and the meter will control according to
the original PID parameters.

V. Fault analysis and troubleshooting

Under normal circumstances, turn on the power switch, and the power indicator does

not light up. After starting up, if the above process is found to be abnormal, it can be
analyzed and handled according to the following situations:

Fault

description

Failure analysis

Troubleshooting

Turn on the

power switch,

the

indicator

Fuse blown

First check whether the

circuit is short-circuited and

replace the insurance