04

Power-On Commissioning

Powering On the UPS

4.1

Turn on the upstream bypass and mains input switches.

After the UPS is powered on, initialization begins. The monitoring display unit (MDU)

displays the Huawei logo and an initialization progress bar.

1. Before powering on the UPS5000, ensure that the check items in the 

UPS5000 Startup 

Service Report

and the post-installation check items are verified.

2. Measure the voltage and frequency of the UPS upstream input switch. The line voltage 

range is 138–485 V AC, and the frequency range is 40–70 Hz.

Initial Startup

4.2

If the UPS is powered on for the first time, you need to obtain the startup password from the

Service Expert app. Skip this step if the UPS is not powered on for the first time.

• The Service Expert app can be downloaded from Google Play Store and can run on Android.

1. Obtain the startup password.

2. Set the language, time, date, network parameters, and system parameters on the Settings 

Wizard screen.

Starting the Inverter

4.3

3. After you perform the settings, the Bypass mode and No battery alarms are reported by the 

MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.

4. If the system has connected to the remote EPO switch, you need to choose Monitoring UPS

System Running Parameter System Settings on the WebUI and set EPO detection to 
Enable.

5. View the system running status diagram on the MDU to check that the UPS is working in 

bypass mode. 

Powering On Loads

4.4

05

Shutting Down the UPS

Set all battery parameters according to the actual situation: Assume that the battery 
specifications are 150 Ah/12 V, 40 batteries are connected in series, and two battery strings 
are connected to the UPS in parallel. Set Single battery voltage(V) to 12Single battery 
capacity(Ah) 
to 150Battery in a battery string to 40, and Number of battery strings to 2.

Download and install the Service Expert app.

After login, tap Power-on password 
activation 
on the screen. A message is 
displayed, indicating whether to start the UPS. 
Tap OK.

Insert the WiFi module into the USB port on 
the MDU. Enable the mobile phone WLAN, 
search for the UPS_WIFI signal, and connect to 
the WiFi signal. The password is Changeme.

Set the Site and Device Type as required, and 
connect the device. Set IP to 192.168.0.10Port
to 443Username to adminPassword to 
Changeme, and click Login.

Enter Bar code and Verification code
obtained from the LCD on the Offline 
Activation 
screen. Tap Generate PWD to 
generate a startup password.

Set Site and Device Type as required, 
and tap Offline Activation.

Enter the generated password in the 
password text box on the LCD to start 
the UPS.

Use the app to 

start the UPS 

online?

Yes

No, start 
the UPS 
offline

On the app home screen, tap StartUp to access the Set Startup screen.

System User

LCD Preset 

Password

WebUI Preset 

Password

admin (system administrator)

000001

Changeme

operator (common user)

000001

Changeme

1. On the main menu, choose Common Functions and tap Inv. ON.
2. In the displayed login window, enter the user name and password, and tap         .
3. In the displayed dialog box, tap Yes to start the inverter.

To ensure system security, 
change the LCD and 
WebUI passwords after 
the first login.

1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears 

from the MDU. 

2. After confirming that the battery strings are properly connected, turn on the battery string 

input circuit breaker. If there are multiple battery strings, turn on the circuit breaker for each 
battery string and then turn on the general circuit breaker between battery strings and the 
UPS. The No battery alarm disappears from the MDU.

3. Turn on the UPS downstream output switch to supply power to the loads.

After you shut down the inverter, the UPS transfers to bypass mode if the bypass is normal; 
the UPS supplies no power if the bypass is abnormal. Before shutting down the UPS, ensure 
that all loads have been shut down.

Powering Off a Single UPS

5.2

Shutting Down the Inverter to Transfer the UPS to Bypass Mode

5.1

1. On the main menu of the LCD, choose Common Functions and tap Inv. OFF.
2. In the displayed login window, enter the user name and password, and tap        .
3. In the displayed dialog box, tap Yes to shut down the inverter.

Turn off the downstream output switch.

Turn off the upstream mains and bypass input switches.

Turn off the battery string circuit breaker of each power unit. If there are multiple 

battery strings, turn off the general circuit breaker between battery strings 

and the UPS and then turn off the circuit breaker for each battery string.

Scan here for more documents:

You can also log in to Huawei technical support website:
https://support.huawei.com/enterprise
https://support.huawei.com

Support

Support-E

WeChat

Copyright ©  Huawei Technologies Co., Ltd. 2021. All rights reserved.

5

Turn on the switches QF and QS in the inductor cabinet.

UPS5000-H-400 kVA & 800 kVA-NTN Quick Guide (Singapore 1-NET, 100 kVA Power Modules)

Summary of Contents for UPS5000-H-400K-NTN

Page 1: ...al injury or equipment damage may occur and the resulting UPS faults are beyond the warranty scope of Huawei 4 This document describes the installation procedure for a single UPS For details about how to install a parallel system contact Huawei technical support Model Weight Dimensions H x W x D UPS5000 H 400K NTN UPS cabinet 800 kg Inductor cabinet 550 kg UPS cabinet 2000 mm x 800 mm x 1000 mm In...

Page 2: ... 100 kVA Power Modules M12 bolt Spring washer Flat washer Expansion sleeve Expansion nut Concrete floor Cabinet Description Unpacking Securing the Cabinet Space planning Bypass input Control module Main switch QF of the inductor cabinet Rectifiers UPS cabinet Inductor cabinet Inductor cabinet UPS cabinet Bypass modules PSU for fans ...

Page 3: ... in the figures are for reference only Do not bind signal cables and power cables together UPS5000 H 400 kVA 800 kVA NTN Quick Guide Singapore 1 NET 100 kVA Power Modules Different power sources Single power source Equipotential ground point Signal cable hole Power cable hole Signal cable route outside the cabinets Signal cable route outside the cabinets Signal cable routing from the inductor cabi...

Page 4: ...ling putty After routing cables and verifying cable connections seal the gap between cables and the cabinet using sealing putty 3 After verifying the installation reinstall all the covers 4 Do not remove the dustproof cover before power on to prevent dust from entering the UPS Cables have been preinstalled and bound in the inductor cabinet The number and colors of cables in the figures are for ref...

Page 5: ...code and Verification code obtained from the LCD on the Offline Activation screen Tap Generate PWD to generate a startup password Set Site and Device Type as required and tap Offline Activation Enter the generated password in the password text box on the LCD to start the UPS Use the app to start the UPS online Yes No start the UPS offline On the app home screen tap StartUp to access the Set Startu...

Reviews: