Installing Cabinets

安装流程

1

Installing Cabinets 

400 kVA

Cabinet Description

Rectifiers

Fan power switch QS

Main switch QF of 

the inductor cabinet

风扇

Power distribution 
cover

功率模块

UPS 
cabinet 

Inductor 
cabinet

Issue: 01
Date: 2021-07-14

1. Before installation, read the user manual carefully to get familiar with product information and safety precautions.
2. Use insulated tools when installing the equipment.
3. Only engineers certified by Huawei or its agent are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage 

may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.

4. This document describes the installation procedure for a single UPS. For details about how to install a parallel system, contact Huawei technical support.

Model

Weight

Dimensions (H x W x D)

UPS5000-H-400K-NTN

UPS cabinet: < 800 kg
Inductor cabinet: < 550 kg

UPS cabinet: 2000 mm x 800 mm x 1000 mm
Inductor cabinet: 2000 mm x 400 mm x 1000 mm

UPS5000-H-800K-NTN

UPS cabinet: < 1300 kg
Inductor cabinet: < 550 kg

UPS cabinet: 2000 mm x 1600 mm x 1000 mm
Inductor cabinet: 2000 mm x 400 mm x 1000 mm

Unpacking

Securing the

Cabinet

Space Planning

M12 bolt

Spring washer

Flat washer

Expansion sleeve

Expansion nut

Concrete floor

Control module

Bypass modules

Power modules

Fans

UPS 
cabinet 

Inductor 
cabinet

PSU for fans

Summary of Contents for UPS5000-H-400K-NTN

Page 1: ...al injury or equipment damage may occur and the resulting UPS faults are beyond the warranty scope of Huawei 4 This document describes the installation procedure for a single UPS For details about how to install a parallel system contact Huawei technical support Model Weight Dimensions H x W x D UPS5000 H 400K NTN UPS cabinet 800 kg Inductor cabinet 550 kg UPS cabinet 2000 mm x 800 mm x 1000 mm In...

Page 2: ... 100 kVA Power Modules M12 bolt Spring washer Flat washer Expansion sleeve Expansion nut Concrete floor Cabinet Description Unpacking Securing the Cabinet Space planning Bypass input Control module Main switch QF of the inductor cabinet Rectifiers UPS cabinet Inductor cabinet Inductor cabinet UPS cabinet Bypass modules PSU for fans ...

Page 3: ... in the figures are for reference only Do not bind signal cables and power cables together UPS5000 H 400 kVA 800 kVA NTN Quick Guide Singapore 1 NET 100 kVA Power Modules Different power sources Single power source Equipotential ground point Signal cable hole Power cable hole Signal cable route outside the cabinets Signal cable route outside the cabinets Signal cable routing from the inductor cabi...

Page 4: ...ling putty After routing cables and verifying cable connections seal the gap between cables and the cabinet using sealing putty 3 After verifying the installation reinstall all the covers 4 Do not remove the dustproof cover before power on to prevent dust from entering the UPS Cables have been preinstalled and bound in the inductor cabinet The number and colors of cables in the figures are for ref...

Page 5: ...code and Verification code obtained from the LCD on the Offline Activation screen Tap Generate PWD to generate a startup password Set Site and Device Type as required and tap Offline Activation Enter the generated password in the password text box on the LCD to start the UPS Use the app to start the UPS online Yes No start the UPS offline On the app home screen tap StartUp to access the Set Startu...

Reviews: