5.7 Transferring to Maintenance Bypass Mode
Context
Installing a lock on the maintenance bypass switch is advised. The lock core has a
diameter of 5–10 mm.
Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
In maintenance bypass mode, the mains supplies power to the loads directly over the
maintenance bypass. If the mains is not normal, the loads may power off.
Procedure
Step 1
Transfer the UPS to the bypass mode by referring to
in
Step 2
Close the maintenance bypass switch by performing the following actions according to the
UPS version being used:
For the UPS5000-E-200K-SM, rotate the handle clockwise 90 degrees (so that the
handle points downwards) as shown in
For the UPS5000-E-200K-FM, remove the barrier chip on the maintenance bypass
switch and close the switch, as shown in
For the UPS5000-E-300K-SM/SMT, rotate the handle clockwise 90 degrees (so that the
handle points leftwards) as shown in
(for the UPS5000-E-300K-SM) and
The
Maint. breaker closed
alarm is displayed in the alarm list, as shown in
. The
UPS transfers to maintenance bypass mode.