5.2 Shutting Down and Powering Off the UPS
Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1
Shut down the inverter.
On the LCD
a.
On the main screen, tap
Common Functions
. Tap
Inv. OFF
.
b.
If no user is not logged in, enter a user name and password, and tap
on
the login screen displayed.
lists the default user names and preset passwords and describes the permission of the
default users.
If an incorrect password is entered three consecutive times, the account will be logged out for 5
minutes.
c.
In the displayed dialog box, tap
Yes
to shut down the inverter.
Figure 5-16
Inv. OFF screen
To shut down the inverter on the
Maintenance
screen, tap
System Info
>
Maintenance
.
On the WebUI
a.
In the browser, enter the UPS IP address in the address box.