![Huawei UPS5000-E-****-FM series User Manual Download Page 139](http://html.mh-extra.com/html/huawei/ups5000-e-fm-series/ups5000-e-fm-series_user-manual_169716139.webp)
UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
4 User Interface
Issue 06 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
130
Figure 4-38
Input Param. screen
Retaining default input parameter settings is advised.
D.G. mode
Set this parameter when a D.G. connects to the input PDC. Select
Enable
when a D.G. is
detected over dry contacts.
D.G. power limiting (kVA)
and
D.G. charger power ratio (%)
Set these two parameters to control the valid input current and limiting input current,
preventing load impact and facilitating better cooperation between the UPS and the D.G.
The value range of
D.G. power limiting (kVA)
is 0–5000 kVA. The default value is 160
kVA for the 125 kVA UPS. The value range of
D.G. charger power ratio (%)
is
0%–100%, and the default value is 0%.
Intra-rack power module start delay (s)
and
Inter-rack power module start delay (s)
These two parameters enable the UPS to control the interval that each rack (or module)
transfers from battery mode to normal mode, which reduces the impact on the generator
or power grid. In the case of battery undervoltage, the system automatically shortens the
delay for transferring to normal mode to 1/8 of the normal delay to accelerate the transfer
and prevent battery overdischarge.
Intra-rack power module start delay (s)
can be set
to a value ranging from 0.5 to 120. The preset value of
Intra-rack power module start
delay (s)
depends on the preset number of power modules. The preset value is 2.0, 1.0,
and 0.5 for 1–5, 6–10, and 10–20 power modules respectively.
Inter-rack power
module start delay (s)
can be set to a value ranging from 2 to 120. The preset value of
Inter-rack power module start delay (s)
is 5.0. The start delay of a module in a rack
varies depending on the rack number and module number. #1 module in rack 1 does not
have a start delay.
Input adaptability
The value of
Input adaptability
can be
Strong
or
Weak
. Strong input adaptability
applies to the D.G. or input sources whose input current has high frequency oscillation.
In this mode, the total distortion of the input current waveform (THDi) is poor, but the
system is stable. Weak input adaptability is suitable for mains and AC input sources. The
default value is
Strong
.
Output Param. screen
Set output parameters, as shown in