UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
74
Figure 3-18
Removing connecting plates
Step 8
Use a manual pallet truck to transport the power cabinet and bypass cabinet to the installation
position. Ensure that the two cabinets align with each other.
----End
3.1.6 (Optional) Combining the Power Cabinet and Bypass
Cabinet (400 kVA, 500 kVA, or 600 kVA UPS)
Procedure
Step 1
Install the bottom, middle, and top connecting plates for the power cabinet and bypass cabinet
based on screw specifications in
Step 2
Install the removed soft copper bars and battery copper bar components based on their
numbers by referring to screw specifications in
Step 3
Reconnect the removed cables to the system signal interface board in the power cabinet, and
bind the cables. For details, see
Step 4
Check that the power cabinet and bypass cabinet are combined completely and securely.
Step 5
After checking that cabinets are combined properly, reinstall the side covers and rear covers.
----End