3.1.3 Preparing Power Cables
NO TICE
● The UPS can generate large leakage currents. A circuit breaker that provides
leakage current protection is not recommended.
● If multiple UPSs are to be connected in parallel, input and output power cables
for each UPS should have the same length and specifications.
lists the recommended cross-sectional areas for UPS power cables. Note
that the currents listed are measured at a rated voltage of 380 V (line voltage).
Table 3-2 Recommended cross-sectional areas for power cables
Item
Specifications
30 kVA
60 kVA
90 kVA
120 kVA
Mains
input
Mains input current (A)
55
110
165
220
UPS5000-E-(30 kVA–120 kVA)-FM