30
Alarm
ID
Alarm
Cause
ID
Alarm
Basic
Register
Address
Bit
Value
0024
1
Battery undertemperature
40163
2
0025
1
Battery overvoltage
40163
3
0027
1
Battery overcurrent
40164
0
0029
1
Maintain battery
40164
1
0036
1
Battery maintenance notification
40164
2
0026
1
Battery undervoltage
40164
3
0086
1
Bypass transfer overlimit
40165
2
0012
1
Bypass neutral loss
40165
6
0096
1
Abnormal ECO voltage
40165
13
0028
1
Breaker OFF
40168
0
0028
2
Breaker OFF
40168
1
0028
3
Breaker OFF
40168
2
0105
5
Communication failure
40168
3
0125
1
Inconsistent parallel parameters
40168
4
61440
1
Flash fault
40168
5
0040
1
Rectifier fault
40169
0
0040
2
Rectifier fault
40169
1
0040
4
Rectifier fault
40169
3
0040
5
Rectifier fault
40169
4
0040
6
Rectifier fault
40169
5
0040
7
Rectifier fault
40169
6
0040
9
Rectifier fault
40169
8
0040
10
Rectifier fault
40169
9
0042
1
Internal fault
40169
13
0042
2
Internal fault
40169
14
0044
1
Incompatible version
40169
15
0044
2
Incompatible version
40170
0
0044
3
Incompatible version
40170
1
0020
1
Battery reverse
40170
2