UPS2000-(6 kVA-20 kVA)
Modbus Protocol Development Guide
2 Modbus Card Signal List
Issue 02 (2016-03-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
28
Signal
Name
Parameter
Type
Range
Gain Register
Address
Address
Length
(Number
of
Digits)
R/W
Attribute
Stop
test*
Unsigned
short integer
(16 bits)
The register
value is fixed at
1.
1
N2023
1
W
The UPS2000A does not support battery tests or the switching between equalized charging and float
charging. The signal name is marked with * to differentiate.
2.2 Alarms
2.2.1 Signal List Description
The definitions for the UPS alarm register addresses comply with the following rules:
Register address: basic register a UPS number x 1024
The range of the UPS number is from 1 to 4.
For example, the register address of the UPS 1 mains abnormal voltage alarm is 40155 + 1024 =
41179 = 0xA0DB; the register address of the UPS 2 mains abnormal voltage alarm is 40155 + 2 x
1024 = 42203 = 0xA4DB.
When the RMS-MODBUS01A card is connected to only one UPS, you can use 0 as the UPS number.
That is, you can directly use the basic register address to query the corresponding value.
If the query is across registers, and a register is not defined in this table, the returned register
value is 0.
2.2.2 Alarm Signal List
Alarm
ID
Alarm
Cause
ID
Alarm
Basic
Register
Address
Bit
Value
0041
1
Rectifier fault
40155
0
0041
2
Rectifier fault
40155
1
0045
3
Charger alarm
40155
4
0045
4
Charger alarm
40155
5
0045
6
Charger alarm
40155
7
0045
7
Charger alarm
40155
8
0045
8
Charger alarm
40155
9