11
Set
Language
(default: English),
System Parameters
, and
Battery Parameters
.
1. The preset password is
000001
, used to enter the
Settings
menu.
2. The default feature code is
999999
, used to restore the preset password.
NOTE
Setting the Input Power Limiting
7.3
Choose
Settings > Battery Parameters
, and set
Input
power limiting
based on the actual situation. Default
value: 5 kW, value range 0.1
–10 kW.
When installing a generator when a power failure occurs,
refer to section 10 and reset
Input power limiting
to the
maximum output capacity of the generator, and
automatically control the battery charge power to avoid
exceeding this limit.
Reset the AC input circuit breaker if its capacity is less than
75 A. The value is the circuit breaker capacity (A) x 100 V x
80%/1000.
NOTE
If you set
Input power limiting
to an excessively smaller value, batteries are not charged, and
this may cause faults.
Note that if you set
Input power limiting
to an excessively larger value, the value may exceed
the capacity of the AC input circuit breaker.