DIP Switch
Setting
Meaning
Default
Setting
S7-4
ON
The reporting rate of the serial port is 19200
bit/s
ON
OFF
The reporting rate of the serial port is 9600
bit/s
Jumpers S1, S2, S3, S8, and S10 are used to set the type of the serial port, and their settings are
described in
Table 3-6
Settings of H303ESC S1, S2, S3, S8, and S11
Jumper
Setting
Meaning
Default
Setting
S1
Pins 1-2 connected
The serial port SIO1 is an
RS-232 port
Pins 2-3
connected
Pins 2-3 connected
The serial port SIO1 is an
RS-422 port
S2
Pins 1-2 connected
The serial port SIO2 is an
RS-232 port
Pins 2-3
connected
Pins 2-3 connected
The serial port SIO2 is an
RS-422 port
S3, S8,
S10
Pins 1-2 of S3, S8, and S10
connected
The serial port SIO3 is an
RS-232 port
Pins 1-2 of all
jumpers
connected
Pins 2-3 of S3 connected;
pins 1-2 of S8 and S10
connected
The serial port SIO3 is an
RS-422 port
Pins 2-3 of S8 and S10
connected, S3 connected in
any way
The serial port SIO3 is an
RS-485 port
S11 is used to set whether the running status LED on the front panel is valid, and the settings
are as described in
Table 3-7
Settings of H303ESC S11
Jumper
Setting
Meaning
Default
Setting
S11
Pins 1-2
connected
The running status LED is valid
Pins 1-2
connected
UA5000 Universal Access Unit
Environment Monitoring
3 H303ESC Monitoring Solution